MODE 4 — IP Address reset:

1.

Apply power to the DMP 64.

2.

Press and hold the reset button about 6 seconds until the reset LED blinks twice.
Release the reset button.

3.

Within (1) second, press the reset button again to reset the IP settings.
If a momentary press does not occur within 1 second, the reset will be ignored.

Mode 4 will:

•

Enable ARP program capability

•

Set the IP address back to factory default (192.168.254.254)

•

Set the Subnet back to factory default (255.255.0.0)

•

Set the Gateway back to factory default (0.0.0.0)

•

Set the Digital I/O Port mapping back to factory default

•

Turn DHCP off

•

Turn Events logging off

MODE 5 — Factory default reset:

1.

Apply power to the DMP 64.

2.

Press and hold the reset button until the reset LED blinks 3 times (~9 seconds),
then release.

3.

Momentarily (<1 second) press the reset button to return the DMP 64 to factory
default conditions.
If a momentary press does not occur within 1 second, the reset is exited.

The default (reset) state of the device is:

•

All mix-points set to 0 dB gain and muted.

•

All outputs active (unmuted, 100% volume).

•

No inserted or active DSP processing.

•

All audio inputs are set to 0 dB gain and muted.

•

All preset and group master memory is clear (empty).

Digital I/O Ports

The dual 4-pin Digital I/O ports monitor or drive TTL level digital signals. The ports consist
of two banks of three I/Os with the fourth pin used as a ground, providing six ports total.
The DSP Configurator software provides selection from a list of scripts, that can be loaded
to the DMP 64. The scripts provide pre-configured sets of functions.
From the main structure menu, click

Tools > Configure Digital IO

to access the scripts

(see

Digital I/O Ports

on page 75).