IMP Pumps NMTC module User Manual

Page 35

Advertising
background image

35


Address Register name

Range

Description

101

ControlReg

b0:

RemoteAccess

Control bit that sets local or remote control.

Setting this bit will enable pump control over

Modbus.

0 = Local

1 = Remote (controlled by Modbus master).

b1:

OnOffReq

Control bit that switches the pump on or off.

0 = Off (stop)

1 = On (start).

b2..15:

RESERVED

-

102

AltControlMode

Alternative Control mode. Use of register 108 is

preferred.

Sets the control mode enumeration.

0 = ConstantRPM

1 = ConstantRPM

3 = ConstantHead

4 = ConstantHead

5 = ConstantHead

6 = ProportionalHead

128 = AutoHeadMode

NOTE:

values outside this range reserved.

103

OperationMode

RESERVED

104

SetPoint

0..

10000

Sets desired pump setpoint.

0 will stop the pump. 10000 will set the pump to

maximum output for desired mode.

Values outside of valid range will cause the pump

to operate with front panel set values.

105

RelayControl

0..2

Configures relay output.

0 = indicates fault

1 = indicates pump ready

2 = indicates pump operation

See section “5 Relay output”.

106..107 RESERVED

108

ControlMode

0..3

Sets the pump control mode.

0 = AutoHeadMode (Automatic head mode)

1 = ProportionalHead (Head proportional to flow)

2 = ConstantHead (Head is kept constant)

3 = ConstantRPM (Speed is kept constant)

NOTE:

values outside this range reserved.

See section “4.2 Control variables” for exact

parameter to be controlled.