IMP Pumps NMTC module User Manual

Page 40

Advertising
background image

40

Error code

Description

Probable cause

E1x

Load errors

E10 (drY)

Low motor load

Low load detected. Pump is

running dry.

E11

High motor load

Motor might be faulty or

viscous medium is present.

E2x

Protection active

E22 (hot)

Converter temperature limit

Circuit is too hot and power

was reduced to less than 2/3 of

rated power.

E23

Converter temperature protection

Circuit is too hot to run, pump

stopped.

E24

Converter overcurrent

Hardware overcurrent

protection triggered.

E25

Overvoltage

Line voltage is too high.

E26

Undervoltage

Line voltage is too low for

proper operation.

E3x

Pump errors

E31

Software motor protection active

Average motor current was too

high, pump load is much higher

than expected.

E4x

Device specific error codes

E40

General frequency converter error

Electrical circuitry did not pass

self-test.

E42 (LEd)

LED faulty

One of the display segment

diodes is faulty (open/short).

E43 (con)

Communications failed

Display board does not detect

proper connection to main

board, but power supply is

present.

E44

DC link current offset

Voltage on DC link shunt (R34)

not in expected range.

E45

Motor temperature outside limits

During MFG. TEST, this is 10k,

1% resistor for 10..30C

During operation, expected
values are -55

°

C..150

°

C.

E46

Circuit temperature outside limits

During MFG. TEST, this is
0..50

°

C.

During operation, expected
values are -55

°

C..150

°

C.

E47

Voltage reference outside limits.

Comparison between internal

references does not match.

E48

15V outside limits

15V supply not 15V.

E49

Test load does not match

No test load detected or

current measurement does not

work properly (MFG. TEST).

E5x

Motor error codes

E51

Motor parameters out of range

Motor does not behave as

expected.

Advertising