Error code
Description
Probable cause
E1x
Load errors
E10 (drY)
Low motor load
Low load detected. Pump is
running dry.
E11
High motor load
Motor might be faulty or
viscous medium is present.
E2x
Protection active
E22 (hot)
Converter temperature limit
Circuit is too hot and power
was reduced to less than 2/3 of
rated power.
E23
Converter temperature protection
Circuit is too hot to run, pump
stopped.
E24
Converter overcurrent
Hardware overcurrent
protection triggered.
E25
Overvoltage
Line voltage is too high.
E26
Undervoltage
Line voltage is too low for
proper operation.
E3x
Pump errors
E31
Software motor protection active
Average motor current was too
high, pump load is much higher
than expected.
E4x
Device specific error codes
E40
General frequency converter error
Electrical circuitry did not pass
self-test.
E42 (LEd)
LED faulty
One of the display segment
diodes is faulty (open/short).
E43 (con)
Communications failed
Display board does not detect
proper connection to main
board, but power supply is
present.
E44
DC link current offset
Voltage on DC link shunt (R34)
not in expected range.
E45
Motor temperature outside limits
During MFG. TEST, this is 10k,
1% resistor for 10..30C
During operation, expected
values are -55
°
C..150
°
C.
E46
Circuit temperature outside limits
During MFG. TEST, this is
0..50
°
C.
During operation, expected
values are -55
°
C..150
°
C.
E47
Voltage reference outside limits.
Comparison between internal
references does not match.
E48
15V outside limits
15V supply not 15V.
E49
Test load does not match
No test load detected or
current measurement does not
work properly (MFG. TEST).
E5x
Motor error codes
E51
Motor parameters out of range
Motor does not behave as
expected.