3 module layout – IMP Pumps NMTC module User Manual

Page 7

Advertising
background image

7

Mode selection switch

Adjustment

10 position rotary

switch

Position read at power-on.

Used for relay configuration and module

configuration reset.

Analog signals (SET1, SET2, SET3)
Input voltage range

-1..32VDC

When used as input.

Output voltage

range

0..12V

When used as output. 5mA max. load allowed

per output.

Input resistance

~100k

0.5mA load is added for most configurations.

Output current sink

range

0..33mA (4-20mA)

Current sink to COM if configured as output.

Relay specifications
Connection type

Screwless terminals

Rating

-

230 VAC, 3 A, AC1

-

32 VDC, 3 A

Potential free changeover contact.

3 Module layout

Modbus signal

SET3 / FB

SET2 / MAX

COM / 0V

SET1 / RUN

A/D +

B/D -

NC

C

NO

RS-485

LED2 / ACT

LED1 / LINK
ETHERNET

MODE

2 1

34

5678

9

0

MAX

RUN

ALARM

Figure 1: Typical module connection