11 pump data register block – IMP Pumps NMTC module User Manual

Page 38

Advertising
background image

38

Address Register name

Description

208

ControlMode

Indicates the actual control mode.

0 = AutoHeadMode (Automatic head mode)

1 = ProportionalHead (Head proportional to flow)

2 = ConstantHead (Head is kept constant)

3 = ConstantRPM (Speed is kept constant).

NOTE:

values outside this range reserved.

See section “4.2 Control variables” for exact parameter to be

controlled.

7.11 Pump data register block

Registers in this block can be read by means of function codes 0x03 and/or 0x04.

They are read-only.

Modbus

address Register name

Range

Resolution Description

301

Head

0.01 m

Pump head estimation in meters of

water column.

302

Flow

0.1 m

3

/h

Pump flow estimation.

303

Efficiency

0.01 %

Estimated pump efficiency.

304

Speed

1 rpm

Motor speed.

305

Frequency

0.1 Hz

Motor frequency

[100.0Hz for 3000rpm and 4 pole

motor].

306..307 RESERVED

308

ActualSetPoint

0..10000 0.01%

Indicates actual setpoint of the pump.

(-1 for internal pump regulation). tbd

309..311 RESERVED

312

313

PowerHI

PowerLO

0..2

32

1 W

Total power consumption of the

system.

314..317 RESERVED

318

CircuitTemp

-5500..

16000

0.01 °C

Power electronics hotspot

temperature.

319

MotorTemp

-5500..

16000

0.01 °C

Motor compartment temperature.

320..321 RESERVED

322

LiquidTemp

-5500..

16000

0.01 °C

Liquid temperature.

323..326 RESERVED

327

328

OperationTimeHI

OperationTimeLO

1 hour

Total operation time (above zero

speed) of the pump.

8

329

330

TotalPoweredTimeHI

TotalPoweredTimeLO

1 hour

Total power-on time of the module.

8

331

RESERVED

332

333

EnergyHI

EnergyLO

1 kWh

Total energy consumption of the

system.

8

8

Not available on all models.