11 pump data register block – IMP Pumps NMTC module User Manual
Page 38
38
Address Register name
Description
208
ControlMode
Indicates the actual control mode.
0 = AutoHeadMode (Automatic head mode)
1 = ProportionalHead (Head proportional to flow)
2 = ConstantHead (Head is kept constant)
3 = ConstantRPM (Speed is kept constant).
NOTE:
values outside this range reserved.
See section “4.2 Control variables” for exact parameter to be
controlled.
7.11 Pump data register block
Registers in this block can be read by means of function codes 0x03 and/or 0x04.
They are read-only.
Modbus
address Register name
Range
Resolution Description
301
Head
0.01 m
Pump head estimation in meters of
water column.
302
Flow
0.1 m
3
/h
Pump flow estimation.
303
Efficiency
0.01 %
Estimated pump efficiency.
304
Speed
1 rpm
Motor speed.
305
Frequency
0.1 Hz
Motor frequency
[100.0Hz for 3000rpm and 4 pole
motor].
306..307 RESERVED
308
ActualSetPoint
0..10000 0.01%
Indicates actual setpoint of the pump.
(-1 for internal pump regulation). tbd
309..311 RESERVED
312
313
PowerHI
PowerLO
0..2
32
1 W
Total power consumption of the
system.
314..317 RESERVED
318
CircuitTemp
-5500..
16000
0.01 °C
Power electronics hotspot
temperature.
319
MotorTemp
-5500..
16000
0.01 °C
Motor compartment temperature.
320..321 RESERVED
322
LiquidTemp
-5500..
16000
0.01 °C
Liquid temperature.
323..326 RESERVED
327
328
OperationTimeHI
OperationTimeLO
1 hour
Total operation time (above zero
speed) of the pump.
329
330
TotalPoweredTimeHI
TotalPoweredTimeLO
1 hour
Total power-on time of the module.
331
RESERVED
332
333
EnergyHI
EnergyLO
1 kWh
Total energy consumption of the
system.
8
Not available on all models.