Page 19: Lsu installation steps

2.2
TS-LLD LSU Installation
LSU Installation Steps
Follow the steps (below) in the order that they appear:
1)
Install the appropriate size MI Cable Adapter on the LSU. Use an adjustable
wrench and a 7/8 inch wrench to tighten the MI cable adapter onto the TS-LLD as
shown in
Figure 2.2-1. NOTE: The cable adapter that you install must match the
size of the junction box plug at the submersible pump housing (two different cable
adapters are shown in
Figure 2.2-1). The 3 inch straight TS-FE cable adapter
must be ordered separately because the pump type and manufacturer varies.
Figure 2.2-1 MI Cable Adapter Installation (before and after)
TS-LLD
LINE LEAK DETECTOR
LEAK SENSING UNIT
(LSU)
TS-FE
3 INCH
M I CABLE
ADAPTER
TS-RJ
2 INCH NPT
M I CABLE
ADAPTER
For FE Petro
Pumps
For Red Jacket
Pumps
Contents:
•
LSU Installation Steps
(Typical in Pump Housing)
•
Overall Site Installation Diagrams (typical Site,
in Angle Check Valve, RedJacket “BigFlo,” & FE
PETRO STP / IST pumps)