1 pmr (pole mount) specifi cations, 0 specifi cations – Alpha Technologies FlexNet PMR, GMR Series User Manual

Page 18

Advertising
background image

18

031-239-C0-003 Rev C

Notes:

1. Additional rack space capacity if batteries are not installed.
2. Runtime of 10 hours based on 212W load and new batteries.
3. * Optionally confi gured items.
4. **Optional items shipped separately.

2.0 Specifi cations

2.1 PMR (Pole Mount) Specifi cations

PMR Component

Description

Enclosures

PMR-S1: 25.5” (64.8cm)W x 32.2” (81.8cm)H x 19.25” (48.9cm)D, Weight: 50 lbs

PMR-S2: 29.5” (74.9cm)W x 37.0” (94cm)H x 19.25” (48.9cm)D, Weight: 60 lbs.

Material

Powder-coated aluminum

Vent Screen

Stainless steel fabric with .008” x .008 (.2mm x .2mm) opening size to minimize snow, water
and dust intrusion

Door and Lid Seal

Neoprene gasketing

Hardware

Stainless steel (excluding optional GemLocks)

Color:

Gray or Pine Green (Custom colors available)

Tamper Switch

Optional

Rack Grounding

Internal ground bar: Eight usable lugs

Safety Ground

Adjacent to AC outlets (Bronze or optional stainless steel ground stud)

Lid

Removable with lanyard

Doors

Hinged lift-off removable with stainless steel spring latch and door-open prop rod; Gemlock
options

Enclosure Mounting

Galvanized steel brackets for wood, and concrete pole mount and wall mount.

Cooling

Natural convection (120VAC and 48VDC fan options)

PMR-S2 with Swing Rack requires these fan kits:

48VDC Fan option ( Alpha p/n: 745-819-20-002)

120VAC Fan option (Alpha p/n: 745-819-21-002)

Internal Mounting Rails

Rack Mounting: EIA 19” mounting rails using Tinnerman mounting clips

PMR-S1: Rail height, 27.5", 14 mounting positions

PMR-S2: Stationary Rack confi guration
(Alpha p/n 745-804-20): Rail height, 33.5", 18 mounting positions

PMR-S2: Swing Rack confi guration
(Alpha p/n 745-797-20): Rail height, 33.5", 14 mounting positions

Rack Grounding

Rails grounded to the chassis (swing rack is isolated from chassis)

Stationary Rack
Adjustment

Provision to move rails on 1” increments over 6” when batteries are not installed.
Forward rail location supports a 12” deep fl ush front mounted panel with a minimum of 3.5” in
front of panel to support fi ber optic connectors.

Swing Rack
Adjustment:

7 mounting holes on 1.00" centers on upper and lower rails.

Enclosure
Environmental Ratings

Equipment space is designed to IP X5 per IEC 529. The enclosure and service entrance is
rated 3R

*Fiber Strain Relief Tie
Bar

19” mounting provides ability to strain relief fi ber cable plugged into the front of
communications equipment.

*Fiber Management
Panel

(Alpha p/n: 745-672-20)

Provides fi ber slack storage and secures a splice tray using a Velcro strap. Tie wrap slots on
sides permit securing fi ber cables to panel. Panel can be removed from enclosure.

**Power Supply

FlexNet ELPM 300 – 300W 48VDC output with 48VDC battery bus and 19-inch reversible
mounting bracket option. (Other UPS systems available.)

**Batteries

48VDC string of 85 GXL (50Ah) positioned on ends (negative terminal side down) with battery
retaining bar. (Other types of batteries available.)

*Battery Cable Kit

Optional

*Battery Heater

Optional (120VAC)

**Form C Alarm Panel

(Alpha p/n: 012-308-20)

Optional. Provides Form C alarm signal interface. Requires the FlexNet ELPM 300-300W
power supply.

*AC Service

External 70A rainproof SUSE rated breaker box with four (4) internal 120VAC 20A receptacles,
or two (2) 120VAC 20A and two (2) 240VAC 20A receptacles

Regulatory

CSA C22.2 No. 107.1-01, CSA C22.2 No. 0-M91, CSA C22.2 No. 0.4-04,

CSA C22.2 No. 94-M91, UL 50, UL 1778

Table 2-1, PMR (Pole Mount) Specifi cations

Advertising