Alpha Technologies FlexNet PMR, GMR Series User Manual

Page 22

Advertising
background image

22

031-239-C0-003 Rev C

Fig. 3-2, Short Wooden Pole Installation

Adhere to local codes regarding pole size, depth of hole, and fi ll material for hole and pedestal. The 8' length
shown below is for reference only. Typically, one-third of the total length of the pole is buried.

3.0 Installation,

continued

3.1

PMR (Pole Mount) Installation, continued

3.1.2 Enclosure on Short Pole with battery vault

You can mount the PMR enclosure on a short wooden pole, in the same manner as
on a standard utility pole, with an Alpha PS-6XL pedestal used as a battery vault. The
accompanying illustrations are for reference, as the exact location of the vault will be
a site-specifi c decision.

NOTE:

NOTE:

Install the pedestal as per the illustrations in Section 3.6 "Installing on a Polymer Pedestal Support".

NOTE:

Ground the system in the same manner as described in the previous section.

1

2

3

4

5

6

7

96.0"

33.5"

30.0"

32.0"

2

1

3

4

5

6

7

Pole mounting bracket centered on 6"x6" pole

Grade

Fill dirt (to grade)

Concrete cap (1/3 of total depth of hole)

3/8" pea gravel (2/3 of total depth of hole)

3" of 3/8" pea gravel

5/8-11 threaded rod (10" long)

Advertising