Proper 240VAC 15A service requires the installation site be:

• Equipped with a 240VAC duplex receptacle to provide power to the Power Supply and peripheral equipment.
• Have a NEMA 6-15R receptacle that is protected by a single, 2-pole, common trip 15A circuit breaker inside

the service entrance.

• Checked to NEC/CEC Code or with your local regulatory authority to verify proper wire AWG (suggested wire

gauge is 14AWG).

• Equipped with a grounding clamp on the enclosure to facilitate dedicated grounding.

Utility Power Connection Notes, continued

LI (Black)

Neutral Bus

LI (Black)

L2 (Red)

Grounding Point Made

to Enclosure Wall

Copper Ground Wire

#8 AWG (Minimum)

Breaker

L2 (Red)

To Utility

Neutral (White)

Typical 240VAC 60 Hz Service Entrance Wiring

When it is required to bond the box to a neutral plate, use the long green bonding screw provided (Alpha P/N

523-011-10, Square D P/N 40283-371-50).

NOTE:

Typical 230VAC 50Hz Service Entrance Wiring

To Utility

Neutral (Blue)

Neutral Bus

To Enclosure

Receptacle

LI (Brown)

LI (Brown)

Grounding Point Made

to Enclosure Wall

Copper Ground Wire

10mm

2

or #8 AWG

(Minimum) (Yellow/Green)

Breaker

Blue

Copper Ground Wire

(Yellow/Green)

13

017-882-B0-001 Rev. C2 (10/2013)