Alpha Technologies XM3-HP Series - Technical Manual User Manual

Page 25

Advertising
background image

25

017-882-B0-001 Rev. C2 (10/2013)

1.0

Introduction

The optional AlphaDOC adds a second isolated

output to the Power Supply. It provides programmable

current limits for two output channels and protects system components by shutting down the load

during overcurrent and short circuit conditions.
The AlphaDOC has a programmable overcurrent threshold (3A-25A) and overcurrent tolerance period

that specifies the time (20-9900ms) an overcurrent condition is permitted before shutting down.
The programmable retry limit can be programmed to select how many times (0-40) after a

programmable delay (5-301 seconds) the AlphaDOC will attempt to reconnect an output once it

has been shut down. When the limit is reached, the XM3 Power Supply automatically retries once

every 30 minutes until the fault clears.
Adding the AlphaDOC to the Power Supply provides these advantages:

A second isolated output: The main purpose of the AlphaDOC is to limit the impact of a

fault condition in one output channel. If a fault condition occurs in a Power Supply (without

the optional AlphaDOC installed) the entire customer network can be affected. The AlphaDOC

option affords protection to one output should a fault condition exist on the other. This gives

you flexibility to isolate Output 1 from Output 2.

A current for critical loads: With the AlphaDOC option, you can designate one output

as the primary connection and the other output as the secondary connection. Commonly,

critical loads are connected to Output 1 as the primary feeder. Using the overcurrent limit

settings, you can ensure the primary output always provides the necessary power. For

example, on a 15 Amp Power Supply, if a customer needs 10 Amps available on Output 1,

the overcurrent limit for Output 2 is set at 5 Amps, so regardless of Output 2, 10 Amps will

remain available for the primary Output 1.

Additional current protection: The standard Power Supply current limit protection is

provided by the fold-back characteristics of the transformer (150% of rated output). The

150% current limit may exceed the ratings of active devices in the cable network and

cause failures. You can lower the maximum current provided at each output by lowering the

overcurrent limit of each respective output. Therefore, to minimize failures due to excess

current supply, set the overcurrent limit to a value below the maximum current the active

components can tolerate.

For example, on a 18A Power Supply, where both outputs are programmed to 10A maximum

and both outputs are supplying 10A, neither output is “in violation” but the total system at 18A

is operating at 111% of its rated output. In this example, after 30 minutes, the Power Supply

will begin a “load shedding” algorithm. The first action is to disconnect Output 2. If this does not

correct the system overload, the next action is to disconnect Output 1.

Power Supply Load

918

All Other Models

Permitted Duration of Load

>125%

>150%

30 seconds

113% to 125%

125% to 150%

10 minutes

108% to 113%

115% to 125%

30 minutes

<108%

<115%

Several months

1.3

Alpha XM3-HP CableUPS Layout, continued

1.3.3 AlphaDOC (PIM)

1.0

Introduction, continued

Table 1-3, Duration of Load

The table below depicts a condition in which no DOC is installed, or no individual output is above

its trip setting.

NOTE:

Advertising