1.2

Theory of Operation, continued
1.2.3 Charger Modes of Operation, continued

The Alpha XM3-HP uses a three-stage (other), four-stage (AlphaCell GXL), or five-stage

(AlphaCell HP) temperature compensated battery charger as determined by the type of

battery used in the system. During AC line operation, the inverter winding on the ferroresonant

transformer feeds the charger circuit which provides the appropriate charge voltages to the

batteries.

3-Stage Charger Modes (BULK/ACCEPT/FLOAT):

The 3-stage charger is applied when the battery type of OTHER is selected in the Smart Display

menu.

BULK charge is a “Constant Current” charge. The maximum current is 10A. As the charge is

returned to the batteries, their voltage increases to a specific threshold (2.40VDC per cell). The

charger then switches to ACCEPT mode. The BULK charger mode generally returns the battery

charge state to 80 percent of rated battery capacity.

ACCEPT charge is a “Constant Voltage” charge. This voltage, default 2.40VDC (programmable

2.20-2.45VDC) per cell, is temperature-compensated to ensure longer battery life and proper

completion of the charge cycle. This cycle is complete when the charging current into the

batteries becomes less than 0.5A or approximately six hours elapses from the time ACCEPT

mode was entered, at which time the charger switches to the FLOAT mode of operation.

FLOAT charge is a temperature-compensated charge, default 2.27VDC (programmable 2.10-

2.35VDC) per cell. During FLOAT mode, the batteries are fully charged and ready to provide

backup power. The charger provides a small maintenance charge to overcome the batteries self-

discharge characteristics and other minor DC loads within the Power Supply.

Battery Voltage

Battery Current

BULK

Constant

Current Mode

(10A max) until

battery voltage

reaches the

ACCEPT level

(2.40V/cell)

ACCEPT

Constant Voltage Mode

(2.40V/cell) until battery

current demand drops

below .5A or time out

based on 4 minutes per

Ah battery capacity

FLOAT

Constant

Voltage Mode

(2.27V/cell)

Fig. 1-2, 3-Stage Charger Modes