0 installation – Alpha Technologies XM3-HP Series - Technical Manual User Manual

Page 42

Advertising
background image

42

017-882-B0-001 Rev. C2 (10/2013)

2.0

Installation

Tools Required:
Small flat-blade screwdriver
Procedure:

1. To access Output Voltage Terminal, remove the

Inverter Module (see Fig. 2-13).

Fig. 2-13, Removing Inverter Module

and Output Voltage Terminal Location

Fig. 2-14, Voltage Wire Position

63V 89V

Output

Voltage

Terminal

Output

Voltage

Wire

Remove all sources of power to unit before performing the following procedure.

WARNING!

2. Loosen the terminal screw and move the Output

Voltage Wire to the desired output voltage position

on the Output Voltage Terminal (see Fig. 2-14).

3. Torque the terminal screw to 7in-lbs (0.79N-m) to

secure the Output Voltage Wire.

4. Replace the Inverter Module.

2.2

XM3-HP Start-Up Procedure, continued

2.2.3 120/240V Configuration Procedure, continued

2.0

Installation, continued

3. Connect the correct power cord to the Power Supply (see Fig. 2-11)

4. Upon start up, the Input Voltage Setting screen will appear. Select correct voltage to proceed

(see

Section 3.3, Smart Display Menus). The Input Voltage Setting screen displays for five

minutes before reverting to the previous settings.

CAUTION!

• If 240V is connected to the Power Supply input when the transformer has the 120V plug installed, the

input circuit breaker will trip.

• If the 120V setting is selected when the input is 240V, the Input Failure alarm will activate and the

Power Supply will transfer to inverter if batteries are connected.

• If the incorrect voltage setting is selected, change the settings by either cycling the power again or

accessing the Input Voltage Setting in the Power Configuration menu.

2.2.4 63/89VAC Output Voltage Reconfiguration Procedure

XM3-918D-HP

90V/0.4A

INP V SETTING

120V

ENTR

h

i

ESC

Fig. 2-12, Input Voltage Setting Screen

120V

240V

Fig. 2-11, Line Cord Plugs