ClimaCool SHC onDEMAND 30, 50, 70, 85 Manual User Manual
Page 18
 
www.climacoolcorp.com
16
Ǥ 
Proper water treatment is a specialized industry and it is 
Ƥ
the water for compliance with the water quality parameters 
listed in Table 1. The materials exposed to the water are 
type 316 stainless steel, pure copper and carbon steel. 
Other materials may exist external to the ClimaCool chiller. 
It is the user’s responsibility to ensure these materials are 
compatible with the treated water. Regular treatment 
of the water will increase longevity of your system. 
	Ƥ
ǯǤ
Ǧ
In such instances whereby the particulates in the water are 
excessive, it is recommended to install an intermediate plate 
and frame heat exchanger to isolate the ClimaCool chiller 
from the building water system. 
Cooling Tower
The cooling tower should be located away from sources of 
external contaminates such as trees, dust or grass cuttings. 
Ƥ
the tower. A periodic visual inspection of the tower system 
should be made and contaminates removed as required.
*(<;065
t &YDFTTJWF$IMPSJOF 6OEJTTPMWFE4PMJETBOE
PUIFSJNQSPQFSXBUFSRVBMJUZDPOEJUJPOT
WILL DAMAGEUIFJOUFSOBMIFBUFYDIBOHFSBOE
WILL VOID YOUR WARRANTY!
WATER CONTAINING
CONCENTRATION
Ammonia
Less than 2.0 mg/l
CaCO
3
Alkalinity
30 - 500 mg/l
CaCO
3
Hardness
30 - 500 mg/l
Chlorides
Less than 200 mg/l
Dissolved Solids
Less than 1000 mg/l
Iron
Less than 5.0 mg/l
Manganese
Less than 0.4 mg/l
Nitrate
Less than 100 mg/l
pH
7.0 - 9.0
Sulphate
Less Than 200 mg/l
͕Ǧ