Electrical connection, Coollogic, Electrical phase sequencing – ClimaCool SHC onDEMAND 30, 50, 70, 85 Manual User Manual
Page 23: Proper voltage balance, Voltage/phase monitor
 
21
www.climacoolcorp.com
Electrical Connection
The power for all modules is taken from a suitable circuit 
breaker/fused disconnect power supply within the main 
panel. The electrical service enters the individual modules 
through the top into the module’s control panel enclosure. 
Proper grounding of the module is mandatory. Before 
ǡ
Ƥ
supply is isolated. A typical power wiring is located on page 
46 – Power Distribution Drawing. Knockout drawings are 
provided. Do not drill into cabinet; shavings can damage 
electronic components. The power for all individual modules 
shall be in compliance with all local and national codes.
CoolLogic
A separate 115 volt power supply is required to power the 
CoolLogic Master Control Panel. Communication between 
the Master Control Panel and chiller modules requires a 
simple two-conductor 18 AWG shielded cable with drain 
rated at 60°C minimum, daisy chain connection. Control 
voltage wiring or with wires that switch highly inductive 
loads such as contactor and relay coils. Refer to the Power 
Distribution schematic on page 46 of this manual for more 
information. All wiring shall be in compliance with all local 
and national codes. 
Electrical Phase Sequencing
Proper clockwise rotation for scroll compressor motors 
is important to prevent damage to the compressors. 
ClimaCool recommends the use of a phase sequence 
indicating instrument following the manufactures 
directions. An alternative is to “bump test” the compressors 
one at a time with pressure gauges attached to the high and 
low gauge ports of the compressors to check for proper 
rotation. Energize the compressor for a few seconds to 
Ƥ
Ǥ
If the discharge pressure does not increase, proper 
rotation is reversed. Compressor rotation can be reversed 
by opening the main electrical disconnect and switching 
any two of the main power supply leads feeding that 
compressor’s contactor.
Proper Voltage Balance
Occasionally, in three phase circuits, a voltage imbalance 
occurs between phases. It is not recommended to operate 
equipment when an imbalance greater that 2% occurs. This 
ơ
their longevity. The following example describes how to 
calculate the average voltage of the three phases to see if 
the imbalance is greater than 2%.
Example: Line 1 = 226v Line 2 = 230v Line 3 = 228v
The average is: (226+230+228) / 3 = 228v
Next, [100(228-226)] / 228 = 0.9%
The voltage imbalance of the three phase circuit is 0.9%. 
This is well under the 2% range. 
Voltage/Phase Monitor
Ȁ
Ƥ
installation with the CoolLogic Master Control Panel. The 
voltage/phase monitor helps guard the chiller bank against 
ƪ
ǡ
conditions which could void your warranty. The voltage/
phase monitor has three wires that connect to the main 
three phase power chiller bank input. Two low voltage 
control wires are connected to the CoolLogic Master Control 
Panel. Do not install control wiring in the same conduit 
as line voltage wiring or with wires that switch highly 
inductive loads such as contactor and relay coils. Note: It 
ȋ͕Ȍ
 
Ǥ͖͖Ǥ
DANGER
 (OHFWULFVKRFNKD]DUG
 0D\UHVXOWLQLQMXU\RUGHDWK
 'LVFRQQHFWSRZHUVXSSO\LHV
EHIRUHVHUYLFLQJ
 5HIHUVHUYLFLQJWRTXDOLILHG
VHUYLFHSHUVRQQHO
 5LVTXHGHFKRFpOHFWULTXH
 5pVXOWDWGHPDLGDQVGRPPDJHV
RXODPRUW
 'HEUDQFKHUDYDQWGҋHQWUHSUHQGUH
OHGpSDQQDJHGHOҋDSSDUHLO
 &RQVXOWHUXQUpSDUDWHXUTXDOLILH
SRXUOHGpSDQQDJH
DANGER
&$87,21
$77(17,21
 8QLWWREHVHUYLFHGE\TXDOLILHG
SHUVRQQHORQO\
 5HIULJHUDQWV\VWHPXQGHU
SUHVVXUH
 5HOLHYHSUHVVXUHEHIRUHXVLQJ
WRXUFK
 5HFRYHUUHIULJHUDQWDQGVWRUHRU
GLVSRVHRISURSHUO\
 &RQILHUODPDLQWHQDQFHiXQ
WHFKQLFLHQTXDOLILH
 /HV\VWpPHIULJRULILTXHVRXV
SUHVVLRQ
 'pFRPSULPHUDYDQWGҋH[SRVHUi
ODIODPPH
 5pFXSHUpUOHIULJRULJHQHHWOH
VWRFNHURXOHGpWULUH
FRUUHFWHPHQW
RECOVER
REFRIGERANT
ATTENTION INSTALLER
͗ 
•If this unit uses a 3 Phase Scroll Compressor, the following
instructions MUST BE followed:
- Unit power supply MUST BE wired in the proper sequence to 
avoid damage to the 3 Phase Scroll Compressor.
- Scroll Compressors with INCORRECT rotation show the
following characteristics:
1.) High sound level;
2.) High suction pressure and low discharge pressure;
3.) Low current draw.
- If any of the three above characteristics exist, swap two of the
three supply wires at the discount and recheck compressor for 
incorrect rotation.
WARNING!
WARNING! To avoid possible injury or death due to electrical 
shock, open the power supply disconnect switch and secure it 
in an open position during installation.
CAUTION!
CAUTION! Use only copper conductors for field installed 
electrical wiring. Unit terminals are not designed to accept 
other types of conductors.