Operation instructions, Control switch, Water resistance – ClimaCool SHC onDEMAND 30, 50, 70, 85 Manual User Manual
Page 44
 
www.climacoolcorp.com
42
Operation Instructions
Flush valve line must be piped to atmospheric pressure such 
ƪǤƪ
any changes in elevation and should be sloped downward in 
the direction of drainage. ƪ
Ǥǣ
	
ǦǤ
Ǥǡ
ơơ
ƪƪǡǦ
ǯȋ
Ƥ
ȌǤ
 
1.
Plug the transformer into a 120-VAC outlet.
2. Insert the 12-VDC plug coming from the transformer into
the jack on the underside of the ATF box.
3. ƪ
control switch (lower switch light should come on the 
valve will start to open).
4. Adjust the “ON TIME” (Valve Open) by turning the
inner timer ring with the GREEN POINTER clockwise to 
increase duration. The ON TIME RANGE is factory set at 
eight seconds. (See Figure 17 on page 41).
5. Adjust the “OFF TIME” (Valve Close) by turning the
outer ring with the RED POINTER clockwise to 
increase duration. The OFF TIME RANGE is factory set 
at twenty-four hours. (See Figure 17 on page 41).
6.   ƪǤơ
 on the timer will come on and the upper light on the 
Ǥƪ
the on light on the timer and the lower switch light will 
come on.
Control Switch
ƪ
down the manual control switch located on the front of 
ȋ	͕͕͘͜ȌǤƪ
control switch can also be used to conveniently drain the 
water out of the strainer before removing the conical screen 
element from the strainer housing. A yellow indicator arrow 
on top of the ATF valve will rotate in sync with the ball 
valve to show the valve position (open or closed). When 
ƪ
ǡ
automatically close.
		ǨǦƤ
Ǥ
ƥ
personal injury. Take precaution when handling.
Water Resistance
The Valve and Controller are water-resistant, but not 
water-proof. Do not install below ground level where the 
component can be submerged in water. Only remove the 
cover plate from the Valve Controller when setting or 
ƪǤ
 
on the unit during normal operation.
ơ 
ơ
ǯơ
pressure. When the strainer element (conical strainer 
Ȍ
Ƥ
ǡ
ơ
Ǧ 
ƪǤ 
alert maintenance personnel that the strainer element 
must be removed and cleaned (See Strainer Element 
Cleaning on page 40).
Figure 20
PSID High
PSID Low
Pressure Differential Alarm (PDA) option
Alarm Reset Button
FRONT
VIEW
LEFT SIDE
VIEW
Power To ATF
110 Volt/12 Volt DC 
Wall Transformer 
Visual
Alarm 
Audible 
Alarm 
Pressure Differential 
Switch-Gauge 
LED Power Indicator
Differential
Set-Point Contact
Cover-Plate Screw (4) in Corners of
Box (DO NOT REMOVE).
Visual
Alarm 
RIGHT SIDE
VIEW
TOP
VIEW
BOTTOM
VIEW
AUX Contacts
(On or Off with Alarm)
Red & Black
Cable Retainer
Operation Instructions
Remove the power supply and insert the connector end into 
the socket on the bottom of the PDA housing (See Figure 
20 above) and plug the transformer into the power source. 
Standard systems are supplied with a 120V power supply to 
the primary of the transformer, with an output secondary of 
͕͖Ǥơ
Ǧ
͛Ǧ͜Ǥơ
͕ƪ
Ǥơ
͛Ǧ͜ǡƤ
clogged and require immediate removal and cleaning. To 
ơ
Ǧǡ
͕Ȁ͕͚dz
ơ
contact to the desired location (See Figure 20). Note: We 
ơ
Ǧ
͕͔Ǥ
Ǥ