Attention installer, Oil type, Oil levels – ClimaCool SHC onDEMAND 30, 50, 70, 85 Manual User Manual
Page 36: Adding oil
 
www.climacoolcorp.com
34
ClimaCool SHC onDemand use scroll compressors. They 
ƥ
Ǥ
contained in this manual will be useful for their care.
All scroll-type machines are unidirectional and will only 
compress in one direction. Operating in the reverse rotation 
can be destructive and will be indicated by a load operating 
noise together with a lack of compression.
Ǧ 
Built into the logic of the CoolLogic Control System is an anti-
short cycle timer which will prevent the compressors from 
restarting immediately following a compressor shutdown. 
͙͛
ơ͖͔͔
Ǥ
 
The compressor operates on a sealed system and oil can 
only be lost if a leak occurs. There are few cases when oil 
will need to be added to a machine in normal operation.
Oil Type
The oil in scroll compressors will be either Polyolester type 
oil (POE) or polyvinyl-ether type oil (PVE). Both refrigerant 
oils require special handling and should be protected 
from contamination. They are extremely hygroscopic and 
will absorb moisture rapidly from the air. It is strongly 
recommended to store and dispense both oils from sealed 
metal cans. ǣ
Ǥơ
Ǥ
Oil Levels
The oil level in the compressor should be checked with the 
compressor running. The compressor oil level may vary 
during operation and particularly on the startup. The normal 
operating compressor oil level should be between Ы and ½ 
of the sight glass. During operation a certain amount of oil 
is carried out into the refrigerant system. The system has 
been designed to bring the oil back to the compressor. If the 
level in the sight glass falls, it may be due to the operating 
conditions and enough time should be given to allow the oil 
to return before more oil is added. This could take up to six 
hours of operation. The compressor should not be allowed 
to operate with less than Я” oil sight glass for longer than 
four to six hours. 
Adding Oil
The compressor must never be ran in a vacuum. A suitable 
hydraulic pump should be used to add oil and reserved for 
this process. Ƥ
Ǥ Oil should only be added to a 
compressor while it is operating to observe valid oil sight 
glass levels. Oil is pressure-injected either into a gauge 
connection on the suction line or injected into the oil 
process port at the bottom of the compressor housing. Only 
enough oil should be added to raise the level above the Ы 
sight glass point.
WARNING
To avoid the release of refrigerant into the atmosphere, 
the refrigerant circuit of this unit must be serviced only by 
WHFKQLFLDQVZKRPHHWORFDOVWDWHDQGIHGHUDOSUR¿FLHQF\
requirements.
All refrigerant discharged from this unit must be recovered 
WITHOUT EXCEPTION. Technicians must follow industry 
accepted guidelines and all local, state and federal statutes for 
the recovery and disposal of refrigerants.
If a compressor is removed from this unit, system refrigerant 
circuit oil will remain in the compressor. To avoid leakage of 
compressor oil, the refrigerant lines of the compressor must 
be sealed after it is removed.
ATTENTION INSTALLER
3 Phase Scroll Compressor Units
t *GUIJTVOJUVTFTB1IBTF4DSPMM$PNQSFTTPS UIFGPMMPXJOH
JOTUSVDUJPOT
MUST BEGPMMPXFE
6OJUQPXFSTVQQMZ
MUST BEXJSFEJOUIFQSPQFSTFRVFODFUPBWPJE
EBNBHFUPUIF1IBTF4DSPMM$PNQSFTTPS
4DSPMM$PNQSFTTPSTXJUI
INCORRECT SPUBUJPOTIPXUIFGPMMPXJOH
DIBSBDUFSJTUJDT
 )JHITPVOEMFWFM
 )JHITVDUJPOQSFTTVSFBOEMPXEJTDIBHFQSFTTVSF
 -PXDVSSFOUESBX
*GBOZPGUIFUISFFBCPWFDIBSBDUFSJTUJDTFYJTU TXBQUXPPGUIF
UISFFTVQQMZXJSFTBUUIFEJTDPOOFDUBOESFDIFDLDPNQSFTTPSGPS
JODPSSFDUSPUBUJPO