Installation, Locating the unit, Floor mounted units – AAON SB-018 User Manual

Page 18: Caution

Advertising
background image

18

Installation

AAON equipment has been designed for

quick and easy installation.

Locating the Unit

Placement of the unit relative to ductwork,

electrical and plumbing must be carefully

considered. Return air plenum or duct can be

mounted directly to the return air flanges.

Use flexible gasket material to seal the duct

to the unit.

Verify floor or foundation can support the

total unit weight, including accessory

weights. Unit must be level in both

horizontal axes to support the unit and

reduce noise and vibration from the unit.

Allow adequate service clearances as shown

on the unit nameplate and unit drawing.

Consult your local building codes for

additional service clearance requirements.

Allow adequate space for piping access and

panel removal. Condenser water piping and

condensate drain connections are located on

either side of the unit.

Figure 2 - SB Series

Table 1 - SB Series Clearances

Location

Minimum

Clearance Required

Access Door Sides

36 inches

All Other Sides

6 inches

Floor Mounted Units

Make sure the unit is level and mounted on a

field supplied platform with a minimum

height to allow for proper depth of the

condensate line p-trap. Other installation

provisions may be necessary according to

job specifications. SB Series vertical air

handling units are designed for up flow

applications only.

Emergency drain pan is

recommended for all applications

where a risk of water damage to

surrounding structure or furnishings.

Refer to local codes.

CAUTION