Filters, Adjusting refrigerant charge, Caution – AAON SB-018 User Manual

Page 31

Advertising
background image

31

Filters

Do not operate the unit without filters in

place. Unit should be checked for correct

filter placement during startup. Operation of

the equipment without filters will result in a

clogged evaporator coil.

Adjusting Refrigerant Charge

Adjusting the charge of a system in the field

must be based on determination of liquid

sub-cooling and evaporator superheat. On a

system with a TXV liquid sub-cooling is

more representative of the charge than

evaporator superheat but both measurements

must be taken.

Before Charging

Unit being charged must be at or near full

load conditions before adjusting the charge.

Units equipped with hot gas reheat must be

charged with the hot gas reheat valves

closed while the unit is in cooling mode to

get the proper charge. After charging, unit

should be operated in reheat

(dehumidification) mode to check for

correct operation.

After adding or removing charge the system

must be allowed to stabilize, typically 10-15

minutes, before making any other

adjustments.

The type of unit and options determine the

ranges for liquid sub-cooling and evaporator

superheat. Refer to the tables below when

determining the proper sub-cooling.

Checking Liquid Sub-Cooling

Measure the temperature of the liquid line as

it leaves the condenser.

Read the gauge pressure at the liquid line

close to the point where the temperature was

taken. Use liquid line pressure as it will vary

from discharge pressure due to condenser

pressure drop.

Convert the pressure obtained to a saturated

temperature using the appropriate refrigerant

temperature-pressure chart.

Subtract the measured liquid line

temperature from the saturated temperature

to determine the liquid sub-cooling.

Compare calculated sub-cooling to the table

below for the appropriate unit type and

options.

Checking Evaporator Superheat

Measure the temperature of the suction line

close to the compressor.

Read gauge pressure at the suction line close

to the compressor.

Convert the pressure obtained to a saturated

temperature using the appropriate refrigerant

temperature-pressure chart.

Before completing startup and

leaving the unit a complete operating

cycle should be observed to verify

that all components are functioning

properly.

CAUTION

The Clean Air Act of 1990 bans the

intentional venting of refrigerant

(CFC’s and HCFC’s) as of July 1,

1992. Approved methods of recovery,

recycling or reclaiming must be

followed. Fines and/or incarceration

may be levied for non-compliance.

CAUTION

Advertising
This manual is related to the following products: