Water piping, Warning, Caution – AAON SB-018 User Manual

Page 21

Advertising
background image

21

Unit is capable of operating with Entering

Water Temperatures (EWT) as low as 57°F

during cooling mode without the need for

head pressure control. If the EWT is

expected to be lower than 57°F or more

stable operation is desired, a factory

provided head pressure control water valve

option is available.

Glycol solution should be used if ambient

temperatures are expected to fall below

freezing or if the loop water temperature is

below 50°F while operating in the heating

mode (heat pump units only). Adding glycol

to condenser water causes an increase in

pressure drop resulting in a decrease in unit

performance. A minimum concentration of

20% glycol solution is recommended.

Table 2 - Glycol Freezing Points

% Glycol

Ethylene

Glycol

Propylene

Glycol

20

18°F

19°F

30

7°F

9°F

40

-7°F

-6°F

50

-28°F

-27°F

Water loop piping runs through unheated

areas or outside the building should be

insulated.

Water Piping

Installing contractor must ensure a

differential pressure switch or water flow

switch is installed between the condenser

water supply and return connections. This

sensor provides a signal to the unit

controller that water flow is present in the

heat exchanger and the unit can operate

without damaging unit components.

Only use approved water pipe material.

Avoid using galvanized material for water

lines/fittings as the material is corrosive and

may cause fouling of the water system.

WATER PRESSURE

Prior to connection of condensing

water supply, verify water pressure is

less than maximum pressure shown

on unit nameplate. To prevent injury

or death due to instantaneous

release of high pressure water, relief

valves should be field supplied on

water piping. Supply water

connection may require a backflow

preventer to prevent supply makeup

water from backing up into the public

water system.

WARNING

WATER FREEZING

Failure of the condenser due to

freezing will allow water to enter the

refrigerant circuit and will cause

extensive damage to the refrigerant

circuit components. Any damage to

the equipment as a result of water

freezing in the condenser is excluded

from coverage under AAON

warranties and the heat exchanger

manufacturer warranties.

WARNING

PVC (Polyvinyl Chloride) and CPVC

(Chlorinated Polyvinyl Chloride) are

vulnerable to attack by certain

chemicals. Polyolester (POE) oils

used with R-410A and other

refrigerants, even in trace amounts,

in a PVC or CPVC piping system will

result in stress cracking of the piping

and fittings and complete piping

system failure.

CAUTION

Advertising
This manual is related to the following products: