Lifting and handling the unit, Refrigerant-to-water heat exchanger water piping, Open loop applications – AAON SB-018 User Manual

Page 19: Warning, Sb series top view

Advertising
background image

19

Figure 3 - SB Series Unit Orientation

Lifting and Handling the Unit

Before lifting unit, be sure that all shipping

material has been removed from unit.

Care should be taken if using spreader bars,

blocking or other lifting devices to prevent

damage to the cabinet, coil or fans.

Refrigerant-to-Water Heat Exchanger

Water Piping

Condenser water pump, condenser water

piping, cooling tower, pressure gauges,

strainers, piping insulation and all

components of the waterside piping must be

field installed.

Open Loop Applications

This product contains one or more

refrigerant-to-water heat exchangers made

of cupronickel or copper and is subject to

severe corrosion and failure when exposed

to chlorides.

UNIT HANDLING

Incorrect lifting can cause damage to

the unit, injury or death. Lifting

equipment capacity should exceed

unit weight by an adequate safety

factor. Always test lift unit not more

than 24 inches high to verify proper

center of gravity lift point.

WARNING

OPEN LOOP APPLICATIONS

Failure of the condenser as a result

of chemical corrosion is excluded

from coverage under AAON Inc.

warranties and the heat exchanger

manufacturer’s warranties.

WARNING

Connections and service

access on right side for

right hand orientation

Right Hand Side

Left Hand Side

Supply Air

Return Air

Compressor and Heat

Exchanger Compartment

SB Series

Top View

Air Flow

Consider the air flow to be

hitting the back of your head.