Caution – AAON SB-018 User Manual

Page 32

Advertising
background image

32

Subtract the saturated temperature from the

measured suction line temperature to

determine the evaporator superheat.

Compare calculated superheat to the table

below for the appropriate unit type and

options.

Table 6 - Acceptable Water-Cooled

Refrigeration Circuit Values

Water-Cooled

Condenser

Sub-Cooling

6-10°F

Sub-Cooling with

Hot Gas Reheat

8-12°F

Superheat

8-15°F

Adjusting Sub-Cooling and Superheat

Temperatures

The system is overcharged if the sub-cooling

temperature is too high and the evaporator is

fully loaded (low loads on the evaporator

result in increased sub-cooling) and the

evaporator superheat is within the

temperature range as shown in the table

above (high superheat results in increased

sub-cooling).

Correct an overcharged system by reducing

the amount of refrigerant in the system to

lower the sub-cooling.

The system is undercharged if the superheat

is too high and the sub-cooling is too low

Correct an undercharged system by adding

refrigerant to the system to reduce superheat

and raise sub-cooling.

If the sub-cooling is correct and the

superheat is too high, the TXV may need

adjustment to correct the superheat.

DO NOT OVERCHARGE!

Refrigerant overcharging leads to

excess refrigerant in the condenser

coils resulting in elevated compressor

discharge pressure.

CAUTION

Thermal expansion valve must be

adjusted to approximately 8-15°F of

suction superheat. Failure to have

sufficient superheat will damage the

compressor and void the warranty.

CAUTION

DO NOT OVERCHARGE!

Refrigerant overcharging leads to

excess refrigerant in the condenser

coils resulting in elevated compressor

discharge pressure.

CAUTION

Advertising
This manual is related to the following products: