Heating coils, Startup, Warning – AAON SB-018 User Manual

Page 27

Advertising
background image

27

The waterside economizer circuit can

operate in three modes: waterside

economizer only, waterside economizer with

mechanical cooling, and mechanical cooling

only.

During waterside economizer only mode of

operation condenser water flows through the

waterside economizer coil with modulating

valves maintaining supply air temperature

setpoint. The condenser water then passes

through water-cooled condenser.

During waterside economizer with

mechanical cooling mode of operation

condenser water flows through the waterside

economizer coil with the waterside

economizer modulating valve fully open.

The condenser water then passes through

water-cooled condenser.

During mechanical cooling only mode of

operation condenser water flows around the

waterside economizer coil with the

waterside economizer bypass valve fully

open. The condenser water then passes

through water-cooled condenser.

Waterside economizer coil condensate drain

outlet drains into evaporator coil drain pan.

See the previous section on evaporator coil

condensate drain piping.

Mineral content of the condenser water must

be controlled. All make-up water has

minerals in it and as the water is evaporated

in the cooling tower, these minerals remain.

As the mineral content of the water

increases, the conductivity of the water

increases.

Field provided and installed water treatment

program must be compatible with stainless

steel, copper, aluminum, ABS plastic, and

PVC. Batch feed processes should never be

used as concentrated chemicals can cause

corrosion. Never use hydrochloric acid

(muriatic acid) or chlorine as it will corrode

stainless steel.

Heating Coils

Factory installed one or two row hot water

and steam heating coils can be factory

mounted. These coils are supplied from a

source through separate piping from the

condenser water source. All controls for

heating operation are field supplied and field

installed.

Always connect the supply to the top of the

coil and the return to the bottom. Water coils

should not be subjected to entering air

temperatures below 38°F to prevent coil

freeze-up. If air temperature across the coil

is going to be below this value, use a glycol

solution to match the coldest air expected.

Startup

(See back of the manual for startup form)

Piping shall be in accordance with

national and local codes. Pressure

limiting devices, backflow preventers

and all other safety requirements are

the sole responsibility of the installing

contractor.

WARNING

Improper installation, adjustment,

alteration, service or maintenance

can cause property damage,

personal injury or loss of life.

Installation and service must be

performed by a qualified installer. A

copy of this IOM should be kept with

the unit.

WARNING