Warning, Caution – AAON SB-018 User Manual

Page 8

Advertising
background image

8

Some chemical coil cleaning

compounds are caustic or toxic. Use

these substances only in accordance

with the manufacturer’s usage

instructions.

Failure to follow

instructions may result in equipment

damage, injury or death.

WARNING

Door compartments containing

hazardous voltage or rotating parts

are equipped with door latches to

allow locks. Door latch are shipped

with nut and bolts requiring tooled

access. If you do not replace the

shipping hardware with a pad lock

always re-install the nut & bolt after

closing the door.

CAUTION

Cleaning the cooling tower or the

condenser water loop with harsh

chemicals, such as hydrochloric acid

(muriatic acid) or chlorine, can

damage the water-cooled condenser.

Care should be taken to avoid

allowing chemicals to enter the

water-cooled condenser. See

Appendix A - Heat Exchanger

Corrosion Resistance for more

information.

CAUTION

OPEN LOOP APPLICATIONS

Failure of the condenser as a result

of chemical corrosion is excluded

from coverage under AAON Inc.

warranties and the heat exchanger

manufacturer’s warranties.

WARNING

WATER FREEZING

Failure of the condenser due to

freezing will allow water to enter the

refrigerant circuit and will cause

extensive damage to the refrigerant

circuit components. Any damage to

the equipment as a result of water

freezing in the condenser is excluded

from coverage under AAON

warranties and the heat exchanger

manufacturer warranties.

WARNING

PVC (Polyvinyl Chloride) and CPVC

(Chlorinated Polyvinyl Chloride) are

vulnerable to attack by certain

chemicals. Polyolester (POE) oils

used with R-410A and other

refrigerants, even in trace amounts,

in a PVC or CPVC piping system will

result in stress cracking of the piping

and fittings and complete piping

system failure.

CAUTION

Advertising