Condensate Drain Piping

Unit may be equipped with more than one

condensate drain pan connection. A p-trap

and drain line must be installed on at least

one section’s drain connection, with the p-

trap not to exceed 6” from the drain

connection. The lines should be the same

pipe size or larger than the drain connection,

include a p-trap, and pitch downward toward

drain. An air break should be used with long

runs of condensate lines.

Draw-through cooling coils will have a

negative static pressure in the drain pan area.

This will cause an un-trapped drain to back

up due to air being pulled up through the

condensate drain piping.

Condensate drain trapping and piping should

conform to all applicable governing codes.

Note: The drain pan connection(s) is a 1”

MPT fitting.

Figure 4 - Drain Trap

The X dimension on the draw-through trap

should be at least equal to the absolute value

of the negative static pressure in the drain

pan plus one inch. To calculate the static

pressure at the drain pan add the pressure

drops of all components upstream of the

drain pan, including the cooling coil, and

add the return duct static pressure. Include

the dirt allowance pressure drop for the

filters to account for the worst-case scenario.

The height from top of the bottom bend of

the trap to the bottom of the leaving pipe

must be at least equal to one half of the X

dimension. This ensures that enough water

is stored in the trap to prevent losing the

drain seal during unit startup

Note: The absolute value of the fan inlet

pressure will always be greater than or equal

to the absolute value of the static pressure in

the drain pan on draw-through units, so the

fan inlet pressure is a safe value to use for

the drain pan static pressure.

Table 5 - Drain Trap Dimensions

Draw-Through

Drain Pan Pressure Trap Dimensions

Negative Static

X

X/2

(inches of water)

(inch)

(inch)

-0.50

1.50

0.75

-1.00

2.00

1.00

-1.50

2.50

1.25

-2.00

3.00

1.50

-2.50

3.50

1.75

-3.00

4.00

2.00

Waterside Economizer

Cooling and pre-cooling waterside

economizer coil is factory installed upstream

of the evaporator coil. Factory tested and

field installed water piping kit includes fully

modulating waterside economizer valve and

fully modulating waterside economizer

bypass valve.

Unit should not be operated without

p-traps. Failure to install a p-trap may

result in overflow of condensate

water.

CAUTION