DE DIETRICH ALEZIO AWHP MIV-II User Manual

Page 21

Advertising
background image

5. Press the key ( to exit the menu.

n Choosing the hybrid operating mode

Parameter Description

Adjustment range

Increment Factory setting

U1

(1)

Hybrid operating mode 0 to 2

4

0 = Off

4

1 = Optimisation of primary energy consumption

4

2 = Optimisation according to energy cost

1

0

(1) Only available if p3 = 0

It is imperative that you input the energy cost parameters
U2

,U3, U4 to use the hybrid operating mode

optimised according to energy cost.

n Energy cost parameters

CAUTION

The currency for parameters U2 ,U3, U4 must be the

same. For example: U2 in euro per kWH and U4 in

euro per litre.

Paramters U2, U3 and U4 are available only if U1

= 2

Parameter Description

Adjustment range Increment Factory

setting

U2

(1)

Tariff per kWh of electricity

4

For a standard electricity tariff, input parameter U2.

0.01 to 2.00

0.01

0.13

U3

(1)

Tariff per kWh of electricity (Off-peak hours)

4

For a Peak Hours / Off-peak Hours electricity tariff, input

parameters U2 for the Peak Hours tariff and U3 for the

Off-peak Hours tariff.

0.01 to 2.00

0.01

0.09

U4

(1)

Fossil energy tariff for the hydraulic back-up.

4

Gas boiler: Tariff per m

3

of gas. For example: €/m

3

4

Fuel oil fired boiler: Tariff per litre of oil. For example: €/litre

0.01 to 2.50

0.01

0.9

(1) Only available if p3 = 0

M003105-A

AWHP MIV-II

4. Operating the appliance

23/04/2013 - 300023321-001-03

20

Advertising