Technical specifications, Heat pump, 7 technical specifications – DE DIETRICH ALEZIO AWHP MIV-II User Manual

Page 28: 1 technical specifications

Advertising
background image

7 Technical specifications

7.1

Technical specifications

7.1.1.

Heat pump

Conditions of use:

4

Limit operating temperatures in Hot mode:

-

Water: +18 °C / +55 °C

-

Outside air: -15 °C / +35 °C

4

Limit operating temperatures in Cooling mode:

-

Water: +7 °C / +25 °C

-

Outside air: +15 °C / +40 °C

4

Maximum operating pressure: 3 bar

AWHP-II

4 MR

6 MR

8 MR

11 MR 11 TR

14 MR 14 TR

16 MR 16 TR

Calorific output

(1)

kW

4.1

5.73

8.08

10.87

10.37

13.07

13.07

14.95

14.95

Performance coefficient (COP)

(1)

4.3

3.93

4.03

4.23

4.15

3.95

3.95

3.82

3.82

Absorbed electrical power

(1)

kWe

0.95

1.46

2.00

2.57

2.50

3.31

3.31

3.91

3.91

Nominal amperage

(1)

A

4.3

6.8

9.3

11.2

6.7

14.8

8.8

17.7

10.1

Calorific output

(2)

kW

4

4.45

5.93

7.57

7.57

10.32

10.32

10.38

10.38

Performance coefficient (COP)

(2)

3.2

3.12

3.12

3.10

3.10

3.10

3.10

3.10

3.10

Absorbed electrical power

(2)

kWe

1.23

1.43

1.90

2.46

2.46

3.37

3.37

3.36

3.36

Cooling output

(3)

kW

3.60

5.40

7.94

10.48

10.48

11.74

11.74

11.70

11.70

Energy efficiency ratio (EER)

(4)(3)

4.65

3.80

3.99

4.68

4.68

4.43

4.43

4.40

4.40

Absorbed electrical power

(4)

kWe

0.77

1.40

1.99

2.24

2.24

2.65

2.65

2.70

2.70

Sound pressure

(5)

dB(A) 36

36

36

40

40

41

41

41

41

Nominal water flow (ΔT = 5K)

m

3

/h 0.71

1.04

1.47

1.88

1.88

2.36

2.36

2.67

2.67

Manometric height available at

nominal flow rate

mbar 450

400

200

300

300

120

120

-

-

Nominal air flow rate

m

3

/h 2100

2100

3000

6000

6000

6000

6000

6000

6000

Power voltage of the outdoor unit V

230 V~ 230 V~ 230 V~ 230 V~ 400 V3~ 230 V~ 400 V3~ 230 V~ 400 V3~

Start-up amperage

A

5

5

5

5.

3

5

3

6

3

Sound output - Inside

(6)

dB(A) 43.2

43.2

40.4

38.2

38.2

40.2

40.2

43.4

43.4

Sound output - Outside

(6)

dB(A) 63.7

63.7

65.2

65.4

65.4

66.8

66.8

69.4

69.4

R410A refrigerant

kg

2.1

2.5

3.6

5

5

5

5

5

5

Refrigeration connection (Liquid-

Gas)

inch

1/4-1/2 1/4-1/2 3/8-5/8 3/8-5/8 3/8-5/8

3/8-5/8 3/8-5/8

3/8-5/8 3/8-5/8

(1) Hot mode: Outside air temperature +7 °C, Water temperature at the outlet +35 °C. Performances in line with EN 14511-2.

(2) Hot mode: Outside air temperature +2 °C, Water temperature at the outlet +35 °C. Performances in line with EN 14511-2.

(3) Only in reversible versions

(4) Cooling mode: Outside air temperature +35 °C, Water temperature at the outlet +18 °C. Performances in line with EN 14511-2

(5) 5 m from the appliance, free field.

(6) Noise spread by the envelope - Test conducted in accordance with the standard NF EN 12102

7. Technical specifications

AWHP MIV-II

27

23/04/2013 - 300023321-001-03

Advertising