6 Troubleshooting

6.1

Error messages

In the event of problems, the control panel displays the symbol a and

an error code.

WARNING

In this instance, note the error code and call the fitter.

The fault code is important for correct and fast tracing of

the nature of the fault and for obtaining support from your

supplier.

To go back to the main display, press the ® key as many times as

necessary. The symbol a continues to be displayed as long as the

error is present.

You can browse in all menus.

Display
error codes

Description

Probable causes

Checking / solution

err

Configuration error

The control system mode is not compatible with the

configuration of the installer parameters.

Contact the fitter.

e[1

flow sensor failure

4

Sensor defective

4

Sensor not or badly connected

Contact the fitter.

e[2

Outside temperature

sensor fault

4

Sensor defective

4

Sensor not or badly connected

Note: The heat pump is based on an outside

temperature of -20°C and only the back-ups are

used.

Contact the fitter.

e[3

Domestic hot water sensor

fault

4

Sensor defective

4

Sensor not or badly connected

Contact the fitter.

e[4

Flow rate fault

The water level and/or pressure are too low

Check the water pressure in

the installation (Pressure

gauge)

Too much air

Completely vent the indoor

module and the installation for

optimum functioning.

e[5

Fault on the outdoor

module

Fault on the outdoor module

Contact the fitter.

M002267-B

AWHP MIV-II

6. Troubleshooting

23/04/2013 - 300023321-001-03