6.2 Error messages

6.2.1

Faults

In the event of a fault, the display may show the following messages.
Contact your fitter.

Message

Probable causes

Solution

24V SHORT-CIRC.

Short circuit 24V

Check the wiring

BURNER FAILURE

Igniter fault

Check the ignition electrode (spacing of the electrodes), its
connector and its connection cable. Replace if necessary.

Ionisation error

Check the earth, Check the ionisation current, If necessary
rectify the level of CO

2

Faulty gas valve

Replace the gas valve

No gas or presence of air in the pipe

Measure the gas supply pressure. Bleed the gas circuit

I-CURRENT FAIL

Ionisation fault during operation

Check the earth, Check the ionisation current, If necessary
rectify the level of CO

2

MCBA FAILURE 5

External influences

Check the wiring

MCBA FAILURE 8

Air pressostat open

Check:
- if the flue gas / combustive air duct is not blocked (i.e.
siphon)
- if the air pressure switch and the connection are blocked

MCBA FAILURE 11

Internal fault

- Check that multi-wire connections are undamaged
- Presence of humidity in the control panel
- Eliminate electro-magnetic influences

MCBA FAILURE 12

Bridge open

- Check the bridge between terminals X4-3 and X4-12 on the
MCBA
- Fuse F2 faulty in the control p.c.b

MCBA FAILURE 30

T maxi exceeded

Check the water flow

MCBA FAILURE 61

Air pressostat closed

Check:
- If Faulty air pressostat
- If the wiring to the air pressure switch is in order
- If the thermal draught is too great

MCBA FAILURE 89

Detection of gas leak V1

The gas sealing control (optional) has detected a leak.
Check whether there is a leak in the gas valve; otherwise
replace the valve.

MCBA FAILURE 90

Detection of gas leak V2

The gas sealing control (optional) has detected a leak.
Check whether there is a leak in the gas valve; otherwise
replace the valve.

MCBA FAILURE XX

Internal safety control box fault

Reset the boiler. Replace the command and safety box.

MCBA.COM.FAULT

Communication error between DIEMATIC
and safety control box

Check the link and the connections between DIEMATIC and
safety control box

ROOM S.A FAIL.
ROOM S.B FAIL.
ROOM S.C FAIL.

EXCHAN.S.FAIL.

OUTL S.B FAIL.
OUTL S.C FAIL.

OUTSI. S.FAIL.

SWIM.P. S.FAIL

Fault in the corresponding sensor

Check the link and the connectors. Replace the sensor if
necessary.
To erase the message, briefly cut off the power to the boiler
using the On/Off switch. Advise the installer. However, you
can operate in manual mode on the part of the installation
concerned. See comments below.

FAN OFF FAIL

The fan is not working

- Faulty fan
- Check the fan wiring (corrosion of the connection)
- Command and safety box faulty

FAN ON FAIL

The fan is working constantly

- Electrical connections broken
- Faulty fan control (replace the fan)