The boiler is now operational, Set the boiler regulation to the desired values, Switch the boiler on and fill in the label "set to – DE DIETRICH C 310 ECO - C 610 ECO User Manual

Page 9

Advertising
background image

9

02/10/07 - 300015183-001-A

C 310 ECO - C 610 ECO

Table of CO

2

- O

2

values

Set the parameter to a value greater than or equal to 8, depending on
the options connected.
Then set the gas seal control pressure switch to a trigger pressure
equivalent to 50% of the admission pressure. Do not forget that the
admission pressure measured does not affect the closing pressure
(higher).
19. Press the Reset key to return the boiler to "user level"
20. Heat the installation to around 80°C and then stop the boiler
21. Bleed the heating installation and Checking the hydraulic

pressure

22. The boiler is now operational
23. Set the boiler regulation to the desired values
24. Switch the boiler on and fill in the label "Set to"



Each individual boiler is delivered with the following fixed
factory settings:

Natural gas H/E

(G20)

Natural gas L/LL

(G25)

High speed (100%)

Low speed (±20%)

High speed (100%)

Low speed (±20%)

Indicative CO

2

value

9,0%

9,0%

9,0%

9,0%

Adjust to

±0,5%

±0,5%

±0,5%

±0,5%

Set to

9,0 ± 0,15%

9,0 ± 0,15%

9,0 ± 0,15%

9,0 ± 0,15%

Indicative O

2

value

4,8%

4,8%

4,8%

4,8%

Adjust to

±0,5%

±0,5%

±0,5%

±0,5%

Set to

4,8 ± 0,25%

4,8 ± 0,25%

4,8 ± 0,25%

4,8 ± 0,25%

P C310-280 (Pa)

1300 ± 100

60 ± 10

1150 ± 100

45 ± 10

P C310-350

1020 ± 100

42 ± 10

840 ± 100

32 ± 10

P C310-430

900 ± 10

50 ± 10

750 ± 100

40 ± 10

P C310-500

1350 ± 100

65 ± 10

1200 ± 100

50 ± 10

P C310-570

1650 ± 100

85 ± 10

1500 ± 100

70 ± 10

Burner regulation

- Modulating, depending on the

outlet temperature

Flow temperature

- 90°C

Advertising