7 Technical characteristics

7.1 C 310 ECO

C 310-... ECO

Unit

280

350

430

500

570

Introduction
Number of sections

5

6

7

8

9

Regulating the output

Modulating

Output (80/60°C) PN

minimum

kW

51

65

79

92

106

maximum

kW

261

327

395

462

531

Output (50/30°C) PN

minimum

kW

56

71

84

98

113

maximum

kW

282

353

427

499

573

Power input

minimum

kW

54

68

82

95

109

maximum

kW

269

336

404

471

539

Combustion gas and by-products
Gas supply pressure

mbar

17 - 25

Gas flow rate Gas H/E (15°C - 1013
mbar)

minimum

m

3

/h

5,7

7,2

8,7

10,1

11,5

maximum

m

3

/h

28,5

35,5

42,7

49,8

57,0

Gas flow rate Gas L/LL(15°C - 1013
mbar)

minimum

m

3

/h

6,6

8,4

10,1

11,7

13,4

maximum

m

3

/h

33,1

41,3

49,7

57,9

66,3

Average nitrogen oxide emission (NOx)

mg/kWh

< 60

Maximum pressure at the flue gas
nozzle

Pa

150

150

150

150

150

Combusted gas flow

minimum

Kg/h

91

114

138

160

183

maximum

Kg/h

453

565

680

793

907

Temperatures of the combusted gases
at 80/60°C

minimum

°C

57

maximum

°C

65

Boiler types:

B23, C33, C53, C63, C83

Heating
Safety temperature

°C

110

Water setting range

°C

20 - 90

Water pressure minimum

bar

0,8

Water pressure maximum

bar

6

Water content

l

49

60

71

82

93

Water resistance at

T = 10°C

mmCE

4520

4400

4800

4400

5000

Water resistance at

T = 20°C

mmCE

1130

1100

1200

1100

1250

Electricity characteristics
Power supply voltage

V/Hz

230 / 50

Power consumption

minimum

W

12

12

12

12

12

maximum

W

303

340

470

600

858

Insulation class

IP

21

Miscellaneous
Weight without water

kg

360

410

460

510

560

Acoustic level at 1 meter

dBA

60

Advertising