BOILER S.FAIL.

Faulty boiler sensor

Check the link and the connectors. Replace the sensor if
necessary.
Reset the boiler.

DHW S. FAILURE

Faulty domestic hot water sensor

Check the link and the connectors. Replace the sensor if
necessary.

SMOKE S. FAIL.

Faulty flue gas sensor

Check the link and the connectors. Replace the sensor if
necessary.
Reset the boiler

BACK S.FAILURE

Faulty return sensor

Check the link and the connectors. Replace the sensor if
necessary.
Reset the boiler

VALVE FAIL

Combined gas valve unit faulty

The safety control box does not signal a gas valve. Check:
- The wiring of the gas valve
- A possible fault in the gas valve (faulty coil)
- Check the wiring. Check that the fuses are in good working
condition.

PARASIT FLAME

Detection of a parasite flame

Check the tightness of the gas circuit. Check the ignition
electrode spacing.
Check that the surface of the burner does not have any fibre
residues.

REARM CVI

Control error

Reset the boiler

STB BOILER

Flow temperature > maximum

Check the wiring.
Bleed the boiler. Check the boiler pump. Check the hydraulic
circuit on the installation.

STB EXCHANGE

Exchanger temperature too high

Check the wiring.
Bleed the boiler. Check the boiler pump. Check the hydraulic
circuit on the installation.

STB SMOKE

Flue gas temperature too high

Heat exchanger fouled

STB BALK

Return temperature too high

Check the wiring.
Bleed the boiler. Check the boiler pump. Check the hydraulic
circuit on the installation.

Message

Probable causes

Solution