6.2.2

(Temporary) blockage



The blockage mode is a normal operating mode and therefore
does not indicate a breakdown but a normal boiler operating
status. A blockage code is likely to signal a technical problem in
the installation or an incorrect setting.

Message

Probable causes

Solution

BL. AIR

Air supply insufficient during pre-ventilation.
A safety lockdown occurs after 5 starts.

- if the flue gas / combustive air duct is not

blocked (i.e. siphon)

- if the air pressure switch and the

connection are blocked

BL.RET.HIGH.BOI

Return temperature > Flow temperature for
10 minutes minimum, after boiler operating at
lower stage

Connection or outlet and return sensor
reversed

BL.SPEED

The maximum temperature increase speed
tolerated in the exchanger has been
exceeded. The boiler is blocked for 10
minutes.
After 5 successive attempts during a single
heating request, the repeated cut-offs will be
saved (the blockage code and the boiler
situation at the time of the blockage).

- Pump
- Water flow
- Hydraulic pressure

BLOCKING b26

Check the bridge between terminals X4-8
and X4-3 in the box

BL.DT BOI BACK

he maximum difference tolerated between
the outlet and return temperatures has been
exceeded. The boiler is blocked for 150
seconds. After 20 successive attempts
during a single heating request, the repeated
cut-offs will be saved (the blockage code and
the boiler situation at the time of the
blockage). However, the boiler does not
break down and continues to operate.

- Pump
- Water flow
- Hydraulic pressure

BL.INT.MCBA

The setting of the parameters is incorrect or
the memory is faulty.

- Configuration of the communication robot

BL.SMOKE

Flue gas temperature > Flue gas
temperature maximum. Trigger 150 seconds.

- Boiler setting
- Fouling

BL.CS OPEN

Blockage input on the CS bridge terminals, is
open, or absence of a bridge.

- External safety and bridge

BL.DT BOI.EXC.

If

T between boiler temperature and

exchanger temperature > 5°C
Trigger 10 Min. seconds. After 5 successive
attempts during a single heating request, the
repeated cut-offs will be saved (the blockage
code and the boiler situation at the time of the
blockage). The boiler will not be locked down.

- Pump
- Water flow

BLOCKING bXX

The control box is off.

Check the wiring
Reset the boiler