Description, Operating principle, Gas/air setting – DE DIETRICH INNOVENS PRO MCA 45 - 65 - 90 - 115 User Manual

Page 10: Combustion, 3 description, 1 operating principle

Advertising
background image

3 Description

3.1

Operating principle

3.1.1.

Gas/air setting

The casing fitted to the boiler is also used as an air box. Air is sucked

in by the fan and gas injected into the venturi by the fan intake. The

fan rotation speed is set according to the settings parameters, the

thermal energy requirement and the temperatures measured by the

temperature sensors. The gas and air are mixed in the venturi. The

gas/air ratio ensures that the quantities of gas and air are adjusted to

each other. This provides optimum combustion on the entire output

range. The gas/air mixture is fed into the burner on top of the

exchanger.

3.1.2.

Combustion

The burner heats the heating water circulating in the heat

exchanger. At a return temperature lower than around 55°C, the flue

gases cool down to a temperature lower than the dew point, thus

causing the condensation of the water vapour contained in the flue

gases in the lower section of the heat exchanger. The heat released

during this condensation process (the latent heat or condensing heat)

is also transferred to the heating water. The cooled combustion gases

are evacuated via the combustion gas outlet flue. The condensation

water is evacuated via a siphon.

3. Description

MCA 45 - 65 - 90 - 115

9

28/08/12 - 300024828-001-01

Advertising