Installation shutdown, Frost protection, 4 installation shutdown – DE DIETRICH INNOVENS PRO MCA 45 - 65 - 90 - 115 User Manual

Page 30: 5 frost protection

Advertising
background image

4.4

Installation shutdown

CAUTION

Do not switch off the mains supply to the appliance. If the

central heating system is not used for a long period, we

recommend activating the HOLIDAYS mode (to ensure

the anti-grip of the heating pump).

4.5

Frost protection

CAUTION

4

The antifreeze protection does not function if the

appliance is switched off.

4

The integrated protection system only protects the

boiler, not the installation. To protect the installation,

set the appliance to HOLIDAYS mode.

The HOLIDAYS mode protects:

4

The installation if the outside temperature is lower than 3°C

(factory setting).

4

The room temperature if a remote control is connected and the

room temperature is lower than 6 °C (factory setting).

4

The domestic hot water tank if the tank temperature is lower

than 4 °C (the water is reheated to 10 °C).

To configure the holidays mode: ¼ See chapter: "Selecting the

operating mode", page 21.

4. Operating the appliance - DIEMATIC iSystem

MCA 45 - 65 - 90 - 115

29

28/08/12 - 300024828-001-01