Code Messages

Description

Checking / solution

B00

BL.CRC.PSU

The PSU PCB is incorrectly

configured

Parameter error on the PSU PCB

4

Contact the professional who takes care of maintenance of

the appliance

B01

BL.MAX BOILER

Maximum flow temperature

exceeded

The water flow in the installation is insufficient

4

Check the circulation (direction, pump, valves)

B02

BL.HEATING
SPEED

The increase in flow temperature

has exceeded its maximum limit

The water flow in the installation is insufficient

4

Check the circulation (direction, pump, valves)

4

Check the water pressure

Sensor error

4

Contact the professional who takes care of maintenance of

the appliance

B07

BL.DT OUTL RET.

Maximum difference between the

flow and return temperature

exceeded

The water flow in the installation is insufficient

4

Check the circulation (direction, pump, valves)

4

Check the water pressure

Sensor error

4

Contact the professional who takes care of maintenance of

the appliance

B08

BL.RL OPEN

The RL inlet on the PCU PCB

terminal block is open

Parameter error

4

Contact the professional who takes care of maintenance of

the appliance

Bad connection

4

Contact the professional who takes care of maintenance of

the appliance

B09

BL.INV. L/N

4

Contact the professional who takes care of maintenance of the appliance

B10
B11

BL.BL INPUT
OPEN

The BL inlet on the PCU PCB

terminal block is open

The contact connected to the BL inlet is open

4

Contact the professional who takes care of maintenance of

the appliance

Parameter error

4

Contact the professional who takes care of maintenance of

the appliance

Bad connection

4

Contact the professional who takes care of maintenance of

the appliance

B13

BL. PCU COM
BL.COM PCU-D4

Communication error with the

SCU PCB

Bad connection

4

Contact the professional who takes care of maintenance of

the appliance

SCU PCB not installed in the boiler

4

Contact the professional who takes care of maintenance of

the appliance

B14

BL.WATER MIS.

The water pressure is lower than

0,8 bar

Not enough water in the circuit

4

Top up the installation with water

B15

BL.GAS PRESS

Gas pressure too low

Incorrect setting of the gas pressure switch on the SCU PCB

4

Check that the gas valve is fully opened

4

Contact the professional who takes care of maintenance of

the appliance

B16

BL.BAD SU

The SU PCB is not recognised

Wrong SU PCB for this boiler

4

Contact the professional who takes care of maintenance of

the appliance

B17

BL.PCU ERROR

The parameters saved on the

PCU PCB are impaired

Parameter error on the PCU PCB

4

Contact the professional who takes care of maintenance of

the appliance

7. Troubleshooting