Installation shutdown, Frost protection, 4 installation shutdown – DE DIETRICH INNOVENS PRO MCA 45 - 65 - 90 - 115 User Manual

Page 35: 5 frost protection

Advertising
background image

1. Press the r key 1 times.
2. The symbol r and the current temperature are displayed (the

temperature flashes, e.g. 60°C).

3. Change the value by pressing the [-] or [+] key. In this example

using key [-] to 55°C.

4. To confirm, press the S key.

5.4

Installation shutdown

CAUTION

Do not switch off the boiler.

If the central heating system is not used for a long period, we

recommend proceeeding as follows:

4

Press key d until OFF is displayed.

4

Press key r until OFF is displayed.

5.5

Frost protection

When the heating water temperature in the boiler is too low, the

integrated boiler protection system starts up. This protection functions

as follows:

4

If the water temperature is lower than 7°C, the heating pump starts

up.

4

If the water temperature is lower than 4°C, the boiler starts up.

4

If the water temperature is higher than 10°C, the boiler shuts down

and the circulation pump continues to run for a short time.

4

If the water temperature in the storage tank is less than 4°C, it is

reheated to its set point.

C003053-A

1x

MCA 45 - 65 - 90 - 115

5. Operating the appliance - IniControl

28/08/12 - 300024828-001-01