Gas Requirements . . .

(Gas Dryers)

NOTE: The gas service to a gas dryer unit must
conform with the local codes and ordinances, or in the
absence of local codes and ordinances, with the latest
edition of the National Fuel Gas Code ANSI Z223.1/
NFPA 54 or the CAN/CGA-B149, National Gas
Installation Code.

Natural Gas, 1,000 Btu/ft

3

(37.3 MJ/m

3

), service must

be supplied at 6.5 ± 1.5 inch water column pressure.

For proper operation at altitudes above 2,000 feet (610 m)
the natural gas valve spud orifice size must be reduced to
ensure complete combustion. See table at right.

L.P. (propane) Gas, 2,500 Btu/ft

3

(97.1 MJ/m

3

), service

must be supplied at 10 ± 1.5 inch water column pressure.

NOTE: DO NOT connect the dryer unit to L.P.
(propane) Gas Service without converting the gas
valve. A 458P3 L.P. (propane) Gas Conversion Kit
must be installed by the Manufacturer’s Authorized
Dealers, Distributors, or local service personnel.

NOTE: The dryer unit and its individual shut-off
valve must be disconnected from the gas supply
piping system during any pressure testing of that
system at test pressures in excess of 1/2 psi (3.45 kPa).

The dryer unit must be isolated from the gas supply
piping system by closing its individual manual shut-off
valve during any pressure testing of the gas supply piping
system at test pressures equal to or less than
1/2 psi (3.45 kPa)

NOTE: When connecting to a gas line, an equipment
shutoff valve must be installed within 6' (1.8 m) of the
dryer. An 1/8" N.P.T. pipe plug must be installed as
shown. See illustration.

Altitude

Orifice Size

Part

Number

ft

m

#

Inches

mm

2000

610

41

0.0960

2.44

503776

3000

915

42

0.0935

2.37

503777

5500

1680

43

0.0890

2.26

503778

7000

2135

44

0.0860

2.18

58719

9000

2745

45

0.0820

2.08

503779

10500

3200

46

0.0810

2.06

503780

To reduce the risk of gas leaks, fire or
explosion:
• The dryer unit must be connected to the

type of gas as shown on nameplate located
in the door recess.

• Use a new flexible stainless steel

connector.

• Use pipe joint compound insoluble in LP

(propane) Gas, or Teflon tape, on all pipe
threads.

• Purge air and sediment from gas supply

line before connecting it to the dryer unit.
Before tightening the connection, purge
remaining air from gas line to dryer unit
until odor of gas is detected. This step is
required to prevent gas valve
contamination.

• Do not use an open flame to check for gas

leaks. Use a non-corrosive leak detection
fluid.

W154R2

WARNING

D233IE2E

3/8" NPT

GAS CONNECTION

1/8" NPT

PIPE PLUG

(For checking

inlet gas pressure)

NEW

STAINLESS

STEEL

FLEXIBLE

CONNECTOR

USE ONLY

IF ALLOWED

BY LOCAL

CODES

(Use

Design A.G.A.

Certified

Connector)

EQUIPMENT

SHUT-OFF

VALVE

Installed within

6' (1.8 m) of dryer

BLACK IRON PIPE
Shorter than 20' (6.1 m) - use 3/8" pipe
Longer than 20' (6.1 m) - use 1/2" pipe