Warning – Alliance Laundry Systems D355IE1B User Manual

Page 31

Advertising
background image

504524

29

• Dryer unit exhaust duct should enter the main duct at an

angle of no more than 30

°

pointing in the direction of

the air flow. Ducts entering the main duct from
opposite sides should be staggered so as not to oppose
each other. See illustration below.

• Provisions should be made for periodic lint removal

and cleaning of the main collector duct.

• The outside end of the main duct should have a weather

hood (with hinged dampers) installed to prevent
passage of weather elements, insects, dust, and dirt into
the dryer units.

• If a weather hood cannot be used, the outside end of the

main duct should have a sweep elbow installed, and be
directed downward as shown on the following page. If
the main duct travels vertically through a roof rather
than through a wall, install 180

°

sweep elbow on the

end of the duct with outlet at least 24 inches (61 cm)
above the highest part of the building.

• Sufficient make-up air must be supplied to replace air

exhausted from dryer units.

NOTE: Where the exhaust duct pierces the wall or
ceiling, an opening having a diameter of 4 inches (10.2
cm) larger than the diameter of the exhaust duct shall
be provided, and the exhaust duct centered within the
opening.

• Damper, Part No. 58786, should be installed in each

dryer’s exhaust system. This will prevent a backdraft
when dryer unit is not in use, and will keep the exhaust
air in balance within the central exhaust system.

IMPORTANT: Provisions must be made for make-up
air.

IMPORTANT: If several dryer units are exhausted
into a main collector duct, it is essential that ductwork
be adequate in size and properly constructed for
efficient operation.

DRYER EXHAUST DUCT

DRYER EXHAUST DUCT

DRYER EXHAUST DUCT

DRYER EXHAUST DUCT

AIR FLOW

MAIN COLLECTOR DUCT

30

°

30

°

30

°

D026IE3A

30

°

To reduce the risk of fire and the
accumulation of combustion gases, DO NOT
exhaust dryer air into a window well, gas
vent, chimney or enclosed, unventilated area,
such as an attic, wall, ceiling, crawl space
under a building or concealed space of a
building.

W045

WARNING

Advertising