Exhaust System

IMPORTANT: Keep exhaust duct as short as
possible.

NOTE: Be certain old ducts are cleaned before
installing your new dryer unit.

For best drying results, recommended maximum length
of exhaust system is shown below.

To prevent backdraft when dryer unit is not in operation,
outer end of exhaust pipe must have a weather hood with
hinged dampers (obtain locally).

NOTE: Weather hood should be installed at least 12
inches (30.5 cm) above the ground. Larger clearances
may be necessary in areas where heavy snowfall can
occur.

Exhaust Direction

The dryer unit can be exhausted to the outdoors through
the back, left, right or bottom of the dryer unit.
EXCEPTION: Gas dryers cannot be vented out the
left side because of the burner housing.

Dryer unit is shipped from factory ready for rear exhaust;
no kits required
.

Exhausting the dryer through sides or bottom (lower
dryer only) can be accomplished by installing a
Directional Exhaust Kit 528P3 available as optional
equipment at extra cost.

WEATHER

HOOD

WITH

HINGED

DAMPERS

RIGID OR

FLEXIBLE

METAL

DUCT

D186IE0A

528P3 Directional Exhaust Kit

Number of

90° Elbows

Weather Hood Type

Recommended

Use only for short run installations

Maximum length of 4" (10.2 cm) diameter rigid metal duct.

0

44 feet (13.4 m)

34 feet (10.4 m)

1

34 feet (10.4 m)

26 feet (7.9 m)

2

26 feet (7.9 m)

20 feet (6.1 m)

3

20 feet (6.1 m)

14 feet (4.3 m)

Maximum length of 4" (10.2 cm) diameter flexible metal duct.

0

24 feet (7.3 m)

20 feet (6.1 m)

1

20 feet (6.1 m)

16 feet (4.9 m)

2

16 feet (4.9 m)

12 feet (3.7 m)

3

12 feet (3.7 m)

8 feet (2.4 m)

NOTE: Deduct 6 feet (1.8 m) for each additional elbow.

D011IE2D

4"

(10.16 cm)

4"

(10.16 cm)

D011IE2E

2-1/2"

(6.35 cm)

(continued)

)