Burkert Type 2033 User Manual

Page 26

Advertising
background image

26

Option: Electrical position repeater

Electrical connection
(see “

Fig. 14: Connection of the appliance socket”).

Pos. Designation of parts
1

Flange sealing

2

Contact insert

3

Cap screw

4

Cap

5

Pressure ring

6

Flat seal

7

Collet

8

Coupling nut

Fig. 14: Connection of the appliance socket

Loosen cap screw

③ on the appliance socket and remove.

NOTE!

Functional failure due to buckled connector lugs preventing
re-installation of the contact insert!
• Carefully remove the contact insert and take care to ensure that

the connector lugs do not become buckled.

Loosen screw in the cap

④ and remove contact insert ②.

Lead cable through coupling nut

⑧.

Make connection as per circuit diagram
(see „

Fig. 15: Electrical WAFitsching“).

Max. rating:

5 A at 250 V AC
0,25 A at 250 V DC.

Assignment: 1.

Input

2. Break contact
3. Make contact

Fig. 15: Electrical WAFitsching

Place contact insert

② in the cap ④ and screw on.

Screw on appliance socket with cap screw

③, assuring proper

seating of the flat seal

⑥.

Test valve for function and leaktightness.