Technical data – Burkert Type 2300 User Manual

Page 7

Advertising
background image

7

Technical data

Typ 2300

B

P

A

Normally open by spring action

I

P

A

Actuating function via reciprocal pressurization

6.2.2. Flow direction below the seat

Depending on the version, the valve is closed against the medium
flow with spring force (control function A, CFA) or with pilot
pressure (control function B or I, CFB or CFI).
As the medium pressure is under the control cone, this pressure
contributes to the opening of the valve.

WARNING!

Medium may be discharged if minimum pilot pressure is too
low or medium pressure too high!
If the minimum pilot pressure is too low for CFB and CFI or the
permitted medium pressure is exceeded, leaks may occur.
• Observe minimum pilot pressure.
• Do not exceed medium pressure (see chapter “Pressure ranges”).

CFA

CFB / CFI

Fig. 1:

Flow direction below the seat
(Rest open/closed, closing against medium)

7. TECHNICAL DATA

7.1. Conformity

Type 2300 conforms with the EC Directives according to the EC
Declaration of Conformity.

7.2. Standards

The applied standards, which verify conformity with the EC Directives,
can be found on the EC Type Examination Certificate and / or the EC
Declaration of Conformity.

7.3. Type label

00203496

2300 A 25M PTFE VA

Tmed -10°C - +185°C

Flow 1 2

Pilot 5,5-7bar

Pmed 16,0bar

W3ZLT

CE

G1" Kvs16,0

CE identification

Permitted pilot pressure

Permitted medium

pressure

Type

Control function (CF)

Orifice of the seat /

actuator size

Sealing material

Body material

Identification

number

Flow direction

Permitted medium

temperature

Date of

manufacture

Main dimensions of

line connection

Flow capacity in standard

production conditions