Burkert Type 2731 User Manual

Page 12

Advertising
background image

diaphragm medium

remarks

EPDM

-10 – +130 °C

Steam sterilization: up to +150 °C

FKM

0 – +130 °C

• dry up to + 150 °C
• otherwise only briefly up

to +150 °C

PTFE

-10 – +130 °C

Steam sterilization: up to +150 °C

Tab. 4: Permitted medium temperature for diaphragms

6.6.2 pressure ranges

Warning!

risk of injury, chemical burns, scalding due to the device
rupturing at excessively high pressure!

▶ Do not exceed the maximum pilot and medium pressure.

▶ Observe permitted ambient and medium temperature.

▶ Observe specifications on the type label.

pilot pressure for valves with pneumatic position controller

To ensure reliable operation with pneumatic position controller,
observe the permitted minimum and maximum pilot pressure!

actuator size [mm]

pilot pressure

ш 80, ш 100, ш 125

5.5 – 7.0 bar

Tab. 5: Pilot pressure for valves with pneumatic position controller

maximum pilot pressure for valves without pneumatic position
controller

actuator size [mm] actuator material

max. permitted pilot
pressure

2)

ш 80, ш 100

PA

10 bar

ø 125

PA

7 bar

ш 80, ш 100, ш 125

PPS

7 bar

Tab. 6: Maximum pilot pressure for valves without pneumatic

position controller

maximum pilot pressure for valves without pneumatic position
controller - only control function B and stainless steel body (Va)

actuator size [mm] actuator material

max. permitted pilot
pressure

2)

ш 80, ш 100, ш 125

PA, PPS

6 bar

Tab. 7: Maximum pilot pressure for valves without pneumatic

position controller - only CFB and stainless steel body (VA)

2)

Observe the maximum pressure range according to the type
label!

12

Technicaldata

english

Type 2730 / 2731 / 2731K