7

insTallaTiOn

7.1

safety instructions

Danger!

danger – high pressure in the equipment!

▶ Before loosening the lines and valves, turn off the pressure and

vent the lines.

Warning!

risk of injury from improper installation!

▶ Installation may be carried out by authorised technicians only

and with the appropriate tools!

risk of injury from unintentional activation of the system and
an uncontrolled restart!

▶ Secure system from unintentional activation.

▶ Following assembly, ensure a controlled restart.

7.2

Before installation

• Before connecting the valve, ensure the pipelines are flush.
• The flow direction is optional.

7.2.1 installation position general

installation for self-drainage of the body

It is the responsibility of the installer and operator to
ensure self-drainage.

installation for leakage detection

One of the bores (in the actuator base) for monitoring
leakage must be at the lowest point.

7.2.2 installation position 2/2-way valve

• The piston-controlled diaphragm control valve can be installed in

any installation position, preferably with the actuator face up.

To ensure self-drainage:

→

Install body inclined by an angle α = 15° – 35° to the horizontal.

→

Observe an inclination angle of 1° – 5° to the line axis.
Forged and cast body: Mark on the body must point upwards
(12 o’clock position, see “Fig. 16”).

→

One of the bores (in the actuator base) for monitoring leakage
must be at the lowest point.

19

Installation

english

Type 2730 / 2731 / 2731K