Technical data

6.6 pneumatic data

Control medium

neutral gases, air

Quality classes in accordance with DIN ISO 8573-1

Dust content Class 5 max. particle size 40 µm,

max. particle density 10 mg/m³

Water content Class 3 max. pressure dew point

- 20 °C or min. 10 °C below the
lowest operating temperature

Oil content

Class 5 max. 25 mg/m³

Temperature range
control medium

-10 – +50 °C

Pressure range
control medium

3 – 7 bar

Air output of pilot valve

250 l

N

/ min

(for aeration and deaeration)
(Q

Nn

- value according to definition for

pressure drop from 7 to 6 bar absolute)

Connections

Plug-in hose connector ∅ 6 mm / 1/4“
Socket connection G 1/8

6.7 electrical data

6.7.1 electrical data without bus control

24 V Dc

Connections

Cable gland M16 x 1.5, wrench size 22
(clamping area 5 – 10 mm)
with screw-type terminals for cable cross-
sections 0.14 – 1.5 mm²

Circular plug-in connector
(M12 x 1, 8-pole)

Pilot valve
Supply voltage

24 V DC ± 10%
max. residual ripple 10 %

Power input

max. 1 W

Output

max. 100 mA per output

Display

max. 20 mA per illustrated illuminated
display (LED)

english