Burkert Type 8691 User Manual

Page 19

Advertising
background image

19

Electrical installation

9.3 Display elements 24 V Dc

note!

Breakage of the pneumatic connection pieces due to rota-
tional impact.

▶ When unscrewing and screwing in the transparent cap, do not

hold the actuator of the process valve but the connection housing.

LED pilot valve (yellow)

Status LED (yellow)

Top LEDs

Connection housing

Fig. 14: Display elements 24 V DC

led

color

top leds

3)

is lit green

End postion bottom

is lit yellow

End postion top

led pilot valve

is lit yellow

Pilot valve is actuated

status led

flashing yellow

Teach function is running

flickers yellow

Puck PCB not available

Tab. 3: Display elements 24 V DC

3)

Color setting ex works. Can be set via jumper (see “Fig. 11: Connection
with cable gland”
).

note!

damage or malfunction due to penetration of dirt and humidity.

▶ To observe degree of protection IP65 / IP67, screw the trans-

parent cap in all the way.

9.4 programming data aS-interface

as-interface
31 slaves

as-interface
62 slaves

I/O configuration

B hex (1 input, 2 outputs)

ID code

F hex

A hex

Extended ID code 1

F hex

7 hex

Extended ID code 2

F hex

E hex

Profile

S-B.F.F

S-B.A.E

Tab. 4: Programming data