7 electrical installation devicenet – Burkert Type 8691 User Manual

Page 23

Advertising
background image

23

Electrical installation

9.7 electrical installation Devicenet

9.7.1 Bus connection (circular connector

m12 x 1, 5-pole, male)

The control head features a 5-pole micro-style circular connector.
The following configuration conforms to the DeviceNet specification.

Connect the control head according to the table.

pin

1

2

3

4

5

signal

Shielding V +

V –

CAN_H

CAN_L

Tab. 8: Pin assignment circular plug-in connector DeviceNet

Pin 4: CAN_H

white

Pin 5: CAN_L

blue

Pin 1: Drain

(Shield)

Pin 3: V–
black

Pin 2: V+
red

Data lines

Supply voltage

11 – 25 V DC

max. power 3 W,
if valve is switched

Fig. 19: View of plug from the front onto the pins, the soldered connections

are behind

9.7.2 configuring the control head

Setting the Dip switches

note!

Breakage of the pneumatic connection pieces due to rota-
tional impact.

▶ When unscrewing and screwing in the body casing, do not hold

the actuator of the process valve but the connection housing.

Unscrew the body casing (stainless steel) in a counter-clockwise
direction.

Body casing

Connection housing

Actuator

Fig. 20: Open control head

english

Type 8691

Advertising