14

Installation

Ensure that the pneumatic connections of the control head
and those of the valve actuator are situated preferably verti-
cally one above the other (see “Fig. 8”).

note!

too high torque when screwing in the fastening screw does
not ensure degree of protection ip65 / ip67.

▶ The fastening screws may be tightened to a maximum torque of

0.5 Nm only.

Attach the control head to the actuator using the two side fas-
tening screws. In doing so, tighten the fastening screws hand-
tight only (maximum torque: 0.5 Nm).

Pilot air outlet 2

1

Pilot air outlet 2

2

Upper pilot air port

Lower pilot air port

Example

∅ 80, CFA

Fig. 8:

Installing the pneumatic connection, 20xx series

Screw the plug-in hose connectors onto the control head and
the actuator.

Using the hoses supplied in the accessory kit, make the pneu-
matic connection between the control head and actuator with
the “Tab. 1: Pneumatic connection to actuator”.

note!

damage or malfunction due to ingress of dirt and moisture.

▶ To comply with degree of protection IP65 / IP67, connect the

pilot air outlet

(only for CFA or CFB) which is not required to the

free pilot air port of the actuator or seal with a plug.

“In rest position” means that the pilot valves of the control head
Type 8691 are isolated or not actuated.

If the ambient air is humid, a hose can be connected between
pilot air outlet 2

2

of the control head and the unconnected

pilot air port of the actuator for control function A or control
function B. As a result, the spring chamber of the actuator is
supplied with dry air from the vent duct of the control head.