PROFIBUS DP start-up

Typ 8750

name

description

identifier

PDI:P1

Pressure before the valve
0000-XXXX depending on sensor
range

GSD file:
PDI:P1
Identifier (HEX):
41, 40, 07

PDI:P2

Pressure before the valve
0000-XXXX depending on sensor
range

GSD file:
PDI:P2
Identifier (HEX):
41, 40, 08

PDI:MTMP Medium temperature

Temperature in °C on 1 °C exactly
Value range 0 °C – 150 °C

GSD file:
PDI:MTMP
Identifier (HEX):
41, 40, 09

PDI:
PCONact

0: Positioner
1: Process controller

GSD file:
PDI:PCONact
Identifier (HEX):
41, 00, 0A

Tab. 24: Process Data Input, PROFIBUS DP

Then input the process data output.

PDO: Process Data Output (from the controller to the process
controller)

name

description

identifier

PDO:
CMD/SP

Process set-point value
(set-point)
Set-point value of process con-
troller in physical unit (as set in the
menu

P.CO INP or P.CO SCAL),

max. value range -999 – 9999,
depending on internal scaling.
If the value is too small or too
large, the last valid value is used
and is indicated in

ERR with HEX

14.

GSD file:
PDO:CMD/SP
Identifier (HEX):
81, 40, 14

PDO:
MODE

Operating state (operation mode)
Value range 0, 1 or 12:
Operating state:
0:

AUTO

1:

MANUAL

12:

BUSSAFEPOS

If the value is too small or too
large, the last valid value is used
and is indicated in ERR with HEX
16.

GSD file:
PDO:MODE
Identifier (HEX):
81, 00, 16