Burkert Type 8750 User Manual

Page 44

Advertising
background image

44

DeviceNet start-up

Typ 8750

name

description of the input data
attributes

attribute
address class,
instance,
attribute; data
type, length

ERR

Error
Indicates the number of the process
value (output) which was not written.
The value is retained until it is deleted
with "1" by acyclically writing the
"Error" attribute (access via Explicit
Message – Set Attribute Single).
HEX
0X14 INP
0X15 SP

100, 1, 1;
USINT, 1 byte

P1

Pressure before the valve in bar

120, 1, 7;
INT, 2 byte

P2

Pressure after the valve in bar

120, 1, 8;
INT, 2 byte

MTMP

Medium temperature in °C

120, 1, 9;
INT, 2 byte

PCONact P.CONTROL active

120, 1, 10;
USINT, 1 byte

Tab. 27: Input data attributes; DeviceNet

14.2.2. static output assemblies

name

address of data
attribute of the
assemblies for
read access. class,
instance, attributes

format of the data
attribute

INP
(factory setting)

4, 21, 3

Byte 0: INP low
Byte 1: INP high

SP

4, 22, 3

Byte 0: SP low
Byte 1: SP high

MTMP

4, 23, 3

Byte 0: MTMP low
Byte 1: MTMP high

SP+MTMP

4, 24, 3

Byte 0: SP low
Byte 1: SP high
Byte 2: MTMP low
Byte 3: MTMP high

MTMP+SP+
ERR+PCON

4, 25, 3

Byte 0: MTMP low
Byte 1: MTMP high
Byte 2: SP low
Byte 3: SP high
Byte 4: ERR
Byte 5: PCON
active

Tab. 28: Static Output Assemblies, DeviceNet

The addresses indicated in “Tab. 28” can be used as a path
statement for the Consumed Connection Path attribute of an I/O
connection.