47

Error messages

Typ 8750

Error messages while the

X.TUNE function is running

display

cause

remedial action

X.TUNE
ERROR 1

No compressed air
connected.

Connect com-
pressed air.

X.TUNE
ERROR 2

Compressed air failure while
X.TUNE is running

Check com-
pressed air
supply.

X.TUNE
ERROR 3

Actuator or control system
deaeration side leaking

Not possible,
device defective.

X.TUNE
ERROR 4

Control system aeration side
leaking.

Not possible,
device defective.

X.TUNE
ERROR 6

The end positions for
POS-MIN and POS-MAX are
too close together.

Check com-
pressed air
supply.

X.TUNE
ERROR 7

Incorrect assignment
POS-MIN and POS-MAX.

To determine
POS-MIN and
POS-MAX, move
the actuator in
the direction
indicated on the
display.

Tab. 32: Error messages during X.TUNE

Error messages while the

P.Q‘LIN / P.TUNE function is running

display

cause

remedial action

P.Q LIN
ERROR 1

No compressed air connected.

No change to process
variable.

Connect compressed
air.
Check process and,
if required, switch on
pump or open the
shut-off valve.
Check process
sensor.

P.Q LIN
ERROR 2

Current node of the valve
stroke was not reached, as
• compressed air supply failed

during

P.Q’LIN.

X.TUNE was not executed.


Check compressed
air supply.
Execute

X.TUNE.

Tab. 33: Error messages during P.Q‘LIN / P.TUNE